connection module (01065)

The picture may show a similar product.

Description

Part No.: 01065000A

CRITO®CrossBoard

connection module

300 mm², for rear feeding of the CrossBoard

3-pole

connection top or bottom

for CrossBoard 800 A 500 - 1100 mm

coming soon

System

CrossBoard® 800 A

Product group 07
Subgroup 48
pack size 1
EAN 4021267010652
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Approvals

Standards

IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Approvals

UL

for UL feeder circuits >250V

type number: CR-B-114-A1

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
Electrical data IEC
rated current (IEC): 800 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 6 kV
rated peak withstand current  Ipk max.: 30 kA
Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) AC: 800 V
max. permitted voltage (IEC) DC: 800 V
current capacity (IEC) max.: 800 A
Details UL
Standards
UL 508
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
rated current (UL): 800 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
for wires UL: Cu 75°C
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
SCCR: 65 kA with any DIVQ/7 circuit breaker 800 A / 480 V AC
100 kA with JDDZ fuse Class L/T 800 A / 600 V AC
Mechanical data
W x H x D: 200 x 200 x 65
weight: 67.0 kg/100
poles: 3-pole
front degree of protection: IP20
Terminal points
screw clamp connection
screw drive: SW13
wire stripping: 30 mm
min. cross-section: 95 mm²
max. cross-section: 300 mm²
Md min.: 4.0 Nm
Md max.: 6.0 Nm
Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
  
min. cross-section UL: AWG 2
max. cross-section UL: MCM 600
torque (UL): 35 - 53 lb-in
for wires UL: Cu 75°C

Application notes

Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
The insulation performance of the article depends on the installation conditions.
for UL feeder circuits >250V

Links

Downloads

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com