Part No.: 33504 000
QUADRON®60Classic Speed
switch disconnector with fuses, 3-pole
box terminal, connection top, for door coupling rotary handle
size 00
double-breaking
operator independent switching (snap-action mechanism)
for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars
System
60Classic
Advantages of the product
With spring-controlled switch mechanism for frequent switching as per utilisation category "A"
FLAG indicator shows the switch setting
Fuses can be changed safely and without tools thanks to double-breaking main contacts
Additional visible separating section by removing the cover incl. fuses
Can be used as mains disconnector as per IEC / EN 60204-1 (main switch)
Also as an Emergency Off switch in combination with the red-yellow door coupling twist handle
Main switch and Emergency Off switch only in combination with AC-23A/B
CrossLink® adapter technology
Simple and safe clicking into place and making contact
Busbar supports can be mounted above each other for flat busbars
Compact dimensions (106mm wide)
Switches can be installed 90° left/right horizontal, always with the same switch lug position
Product group | 15 |
Subgroup | 20 |
pack size | 1 |
EAN | 4021267335045 |
ECLASS 6.1 | 27371401 |
ECLASS 7.1 | 27371401 |
ETIM 4.0 | EC001040 |
ETIM 5.0 | EC001040 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
type number: QCS-NH00
for fuse links size: | NH 000, NH 00 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 10 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Details IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
rated current (IEC): | 125 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 800 V |
rated surge voltage Uimp : | 8 kV |
Utilisation category AC (IEC 60947-3) : | AC-23B (690V/125A) AC-23A (500V/125A) AC-22A (690V/125A) AC20B (800V) visible information required: do not switch under load |
Utilisation category DC (IEC 60947-3) : | DC specifications: 2 current paths (L1,L3) in series DC-22B (220V/125A) DC-20B (800V) at pollution degree 3 visible information required: do not switch under load |
cond. short-circuit current with fuses (AC): | 50 kA / 690 V (125A) |
approved wth fuse links of operation class: | gG |
Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals. | |
When several devices are used side-by-side in continuous operation, the rated load factor specified in VDE 0660 Part 500 / EN 60 439-1, Table 1, must be observed. |
Mechanical data | |
W x H x D: | 106 x 200 x 155 |
weight: | 208.0 kg/100 |
poles: | 3-pole |
for busbars: | 12, 15, 20, 25, 30 x 5, 10 and section busbars |
Terminal points | |
cage clamp connection | |
screw drive: | S4 |
wire stripping: | 20 mm |
min. cross-section: | 1.5 mm² |
max. cross-section: | 70 mm² |
re: | 1.5 - 10 mm² |
f: | 1.5 - 70 mm² |
f + AE: | 1.5 - 70 mm² |
(f + AE may not fit with max. cross-section) | |
Md min.: | 5.0 Nm |
Md max.: | 6.0 Nm |
Not suitable for aluminium cables ! | |
Terminal space: | 13x13 |
lam. Cu width: | 9 - 13 mm |
lam. Cu thickness: | 1 - 10 mm |
Not suitable for aluminium cables ! | |
permitted power dissipation of the fuse-link: | 10 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
33914
000
connecting terminal 120 mm²
front connection
for: QCS-NH00, QCS-160
More
33908
000
pilot switch for monitoring the switch position
changeover 250 V AC / 5 A, 30 V DC / 4 A
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320
More
33910
000
door coupling rotary drive
black, with handle
door interlock can be activated, for padlocks
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320
More
33911
000
door coupling rotary drive
yellow-red, with handle
door interlock can be activated, for padlocks
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320
More
33912
000
extension shaft, 290 mm long
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320
More
33913
000
extension shaft, 490 mm long
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320
More
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com