Description

Part No.: 31232000

SECUR®60Classic PowerLiner

busbar mounted switch-disconnector-fuse

for fuses 10x38 IEC 60269-2

3P

connection bottom

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

3-pole / 1-pole switching

System

60Classic

Product group 01
Subgroup 42
pack size 1
EAN 4021267312329
ECLASS 6.1 27142190
ECLASS 7.1 27142190
ETIM 4.0 EC002705
ETIM 5.0 EC002705

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

type number: SPL-10x38

Technical data

for fuse links size: 10x38
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 3 W
Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
rated current (IEC): 32 A
rated voltage (IEC) AC: 690 V
rated voltage (IEC) DC: 110 V
rated isolation voltage Ui AC: 500 V
rated isolation voltage Ui DC: 250 V
rated surge voltage Uimp : 6 kV
Utilisation category AC (IEC 60947-3) :

AC-23A (400 V)
AC-22A (690 V)

cond. short-circuit current with fuses (AC): 50 kA / 400 V (32A)
approved wth fuse links of operation class: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 3.4 W.

(The power dissipation at full load would be 5.3 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) AC: 725 V
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
for fuse links gG and aM as per IEC / EN 60269-2

The function of isolation between incoming and outgoing contacts is provided by the opening of the switching mechanism as required in the standard.

Mechanical data
W x H x D: 27 x 220 x 100
weight: 76.0 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
front degree of protection: IP20

Type of fastening: patented click mechanism

Terminal points
cage clamp connection
screw drive: PZ2
wire stripping: 12 mm
min. cross-section: 1.5 mm²
max. cross-section: 16 mm²
Md min.: 2.0 Nm
Md max.: 2.5 Nm
Not suitable for aluminium cables !

Application notes

Not suitable for aluminium cables !
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
permitted power dissipation of the fuse-link: 3 W

Links

Downloads

Accessories

31901000
side-mounted module
More

31902000
reducer D02 for D01 fuses 2 - 16 A
More

31903000
pilot switch
changeover 250 V AC / 5 A, 30 V DC / 4 A