Company
Innovationen
Products
The picture may show a similar product.
Part No.: 23053000AD
CAPUS®Panel
switch-disconnector 2-pole
screw M10, without handle
400 A
IEC version
for mounting plate
coming soon
System
Panel
Product group | 14 |
Subgroup | 07 |
pack size | 1 |
EAN | 4021267230531 |
ECLASS 6.1 | 27371403 |
ECLASS 7.1 | 27371403 |
ETIM 4.0 | EC000216 |
ETIM 5.0 | EC000216 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020
Approvals
IEC (CB) , VDE
type number: DC_SWITCH
size: | 1 |
Details IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 |
Electrical data IEC | |
rated current (IEC): | 400 A |
rated voltage (IEC) DC: | 1500 V |
rated isolation voltage Ui DC: | 1500 V |
rated surge voltage Uimp : | 12 kV |
cond. short-circuit current with fuses (DC): | 40kA (1500V In 500A) |
approved wth fuse links of operation class: | gPV |
rated short-time withstand current Icw (1.0 s) max.: | 15 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 7.0 W.
(The power dissipation at full load would be 11.0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) DC: | 1500 V |
current capacity (IEC) max.: | 400 A |
Gebrauchskategorien siehe Datenblatt (unter Downloads) |
Mechanical data | |
W x H x D: | 121 x 151 x 158 |
weight: | 286.0 kg/100 |
poles: | 2-pole |
Mounting: | for mounting plate |
vertical installation position: | Yes |
horizontal installation position: | Yes |
Terminal points | |
min. cross-section: | 10 mm² |
max. cross-section: | 240 mm² |
all poles switched at the same time