switch-disconnector 3-pole (33540)

The picture may show a similar product.

Description

Part No.: 33540 000

QUADRON®60Classic Speed

switch-disconnector 3-pole

box terminal, connection bottom

160 A

double-breaking

operator independent switching (snap-action mechanism)

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

System

60Classic

Advantages of the product

With spring-controlled switch mechanism for frequent switching as per utilisation category "A"
Lockable in neutral position with up to 3 padlocks
FLAG indicator shows the switch setting of double interrupting main contacts
Can be used as a mains disconnector as per IEC / EN 60204-1 (main switch)
Main switch only in combination with AC-23A/B
AC-23B (690V/125A), AC-23A (500V/125A)

CrossLink® adapter technology
Simple and safe clicking into place and making contact
Busbar supports can be mounted above each other for flat busbars

Compact dimensions (106mm wide)

Product group 14
Subgroup 20
pack size 1
EAN 4021267335403
ECLASS 6.1 27371403
ECLASS 7.1 27371403
ETIM 4.0 EC000216
ETIM 5.0 EC000216

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

Approvals

IEC (CB)

type number: QCS-160

Technical data

Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
rated current (IEC): 160 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 8 kV
Utilisation category AC (IEC 60947-3) : AC-23B (690V/125A)
AC-23A (500V/125A)
AC-22A (690V/160A)
Utilisation category DC (IEC 60947-3) :

DC specifications: 2 current paths (L1,L3) in series
DC-22B (220V/125A)

cond. short-circuit current with fuses (AC): 50 kA / 690 V (125 A)
approved wth fuse links of operation class: gG
rated short-time withstand current Icw (1.0 s) max.: 4.5 kA
rated making capacity: 7 kA

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 26.7 W.

(The power dissipation at full load would be 41.8 W.)

Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals.
When several devices are used side-by-side in continuous operation, the rated load factor specified in VDE 0660 Part 500 / EN 60 439-1, Table 1, must be observed.
Mechanical data
W x H x D: 106 x 200 x 128
weight: 216.0 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
Terminal points
cage clamp connection
screw drive: S4
wire stripping: 20 mm
min. cross-section: 1.5 mm²
max. cross-section: 70 mm²
re: 1.5 - 10 mm²
f: 1.5 - 70 mm²
f + AE: 1.5 - 70 mm²
(f + AE may not fit with max. cross-section)
Md min.: 5.0 Nm
Md max.: 6.0 Nm
Not suitable for aluminium cables !
Terminal space: 13x13
lam. Cu width: 9 - 13 mm
lam. Cu thickness: 1 - 10 mm

Application notes

Not suitable for aluminium cables !

Links

Downloads

Accessories

connection accessories

33914 000
connecting terminal 120 mm²
front connection
for: QCS-NH00, QCS-160
More

further accessories

33908 000
pilot switch for monitoring the switch position
changeover 250 V AC / 5 A, 30 V DC / 4 A
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com