NH fuse switch-disconnector size 00, 160 A, panel mounting (33208)

The picture may show a similar product.

Description

Part No.: 33208000

QUADRON®Panel

NH fuse switch-disconnector size 00, 160 A, panel mounting

screw M8

with electromechanical fuse monitoring

for mounting plate

System

Panel

Advantages of the product

For safe connection of the leads, the shock protection is split into 2.

Product group 09
Subgroup 04
pack size 1
EAN 4021267332082
ECLASS 6.1 27142108
ECLASS 7.1 27142108
ETIM 4.0 EC001040
ETIM 5.0 EC001040

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

UL 4248-1

Approvals

IEC (CB) , UL , CCC

for UL feeder circuits >250V

type number: LTS-00

UL file: E230163, UL category (for USA): IZLT2 https://www.ul.com

CCC certificate: 2004010302117250

Technical data

for fuse links size: NH 000, NH 00
fuse links acc. to standard: IEC / HD 60269-2
live grip lugs required: Yes
permitted power dissipation of the fuse-link: 12 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
rated current (IEC): 160 A
rated voltage (IEC) AC: 690 V
rated voltage (IEC) DC: 250 V
rated isolation voltage Ui AC: 800 V
rated isolation voltage Ui DC: 250 V
rated surge voltage Uimp : 6 kV
Utilisation category AC (IEC 60947-3) : AC-23B (400 V)
AC-23B (500 V / 125A)
AC-22B (690 V)
AC-21B (690 V)
Utilisation category DC (IEC 60947-3) : DC specifications: 2 current paths (L1,L3) in series
DC-22B (250V)
cond. short-circuit current with fuses (AC): 50 kA / 690 V
approved wth fuse links of operation class: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 4,5 W.

(The power dissipation at full load would be 7,0 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) AC: 725 V
max. permitted voltage (IEC) DC: 262 V
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
for fuse links IEC 60269-2-1 (I) / DIN VDE 0636-201 size 00 up to 12W power dissipation, with grip lugs under voltage
Entsprechend den angegeben AC- und DC- Schalteigenschaften und unter Berücksichtigung der Überlastbedingungen, sind gewisse Abstände zu geerdeten Metallteilen einzuhalten. Nähere Informationen auf Anfrage.
Bei Verwendung als Trennschalter ist die Einhaltung der Abstände nicht erforderlich
Degree of protection IP30 at front, degree of protection near terminal depends on installation
fuse monitoring:
rated operating voltage
AC 24-690V, DC 24-250V
potential-free opener and closer:
AC-15 24V/2A, (230V* 0.5A)
DC-13 24V/1A, 60V 0.15A

*pollution degree 2, surge category II
auxiliary energy not required,
for further information, see assembly manual
Details UL
Standards
UL 4248-1
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 160 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR: 100 kA
Mechanical data
W x H x D: 106 x 176 x 157
weight: 126,0 kg/100
poles: 3-pole
Mounting: for mounting plate
front degree of protection: IP30
Terminal points
screw connection
M8
screw drive: SW13
Md min.: 8,0 Nm
Md max.: 10,0 Nm
Not suitable for aluminium cables !
  

Accessories:
Clamp connection:  Cu 1.5-70mm² s(r), f+AE; lam. Cu 12x1-10; 3Nm torque
single wedge clamp terminal: Cu, Al* 16-70mm² s(r), s(s), f+AE; 3Nm torque
tunnel terminal 3x Cu 1.5-16mm² s(r), f+AE; 3Nm torque

*Connections not maintenance-free if aluminium conductors are used.

Application notes

Not suitable for aluminium cables !
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
live grip lugs required: Yes
permitted power dissipation of the fuse-link: 12 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
for UL feeder circuits >250V

Links

Downloads

Accessories

01182000
tunnel terminal for screw connection M8
1x 2.5 - 16 mm² + 2x 2.5 - 25 mm²
NH 00
More

03727000
clamp connector
1.5 - 70 mm²
size 00
More

03849000
lid interlock
for sealing wire
Size 00
More

30894000
M8 screw connector
with spring washer
size 00
More

33156000
pilot switch
changeover 250 V AC / 5 A, 30 V DC / 4 A
More

33193000
rapid mounting set
for 2 mounting rails, rails centre distance 125 mm or 150 mm
size 00
More

33224000
prism terminal, single, for Cu cables
16 - 70 mm²
NH 00
More

78105000
trim frame, double
232 x 210, not for 33221, 33222
size 00
More

78893000
trim frame, single
130 x 210, not for 33221, 33222
size 00
More

79811000
cover for cable lugs, top / bottom attachable
NH 00
for: 33200, 33208, 33329, 33394, 33398, 33420
More

Usage

32001000
EQUES®100Energy
busbar adapter 160 A
108 x 315
for busbars: 30, 40, 50, 60 x 10
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com