Innovationen
产品
The picture may show a similar product.
订货号 31961000
AMBUS®60Classic
熔断器座,母线式,690 V
适用熔断体 10 x 38,IEC 60269-2
10 x 38 / 2 极
适用母线 12, 15, 20, 25, 30 x 5, 10 和异型母线
系统
60Classic
产品组 | 01 |
分组 |
46 |
包装件数 | 6 |
EAN | 4021267319618 |
ECLASS 6.1 | 27142190 |
ECLASS 7.1 | 27142190 |
ETIM 4.0 | EC002705 |
ETIM 5.0 | EC002705 |
标准
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
认证许可
IEC (CB) , VDE
型号: AEL10x38
for fuse links size: | 10x38 |
fuse links acc. to standard: | IEC / HD 60269-2 |
所使用熔断器的允许损耗功率: | 3 W |
Details IEC | |
标准 | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
额定电流(IEC): | 32 A |
额定电压(IEC)AC: | 690 V |
额定电压 (IEC) DC: | 440 V |
额定冲击耐受电压 Uimp: | 6 kV |
带熔断器测定的工作等级: | gG |
带熔断器时的分断能力: | 20 kA |
功率输出:
The power dissipation at a typical load of 80 % results to 0.4 W.
(The power dissipation at full load would be 0.7 W.)
Supplementary data IEC | |
下述参数已经在特定条件下通过测试得到验证。开始设计之前,请联系维纳尔咨询这些条件。 |
最大电压 IEC AC: | 725 V |
最大电压 IEC DC: | 462 V |
符合 IEC 60947-3 的熔断器组合电器,只有在作为没有分断能力的熔断器式隔离器时、在不超过额定绝缘电压使用并进行相应的标识时,才允许超过额定工作电压运行。 |
适用熔断器, 符合 IEC / EN 60269-2标准 (gG, 最大 3W) |
机械数值 | |
宽 x 高 x 厚: | 27 x 140 x 63 |
重量: | 12.2 kg/100 |
极数: | 2线 |
适用母线: | 12, 15, 20, 25, 30 x 5, 10 和异型母线 |
固定方式: 获得专利的卡接机构
连接端 | |
Not suitable for aluminium cables ! | |
符合IEC标准: 铜 1.5 … 6 mm2 (f, re) |
Not suitable for aluminium cables ! | |
符合 IEC 60947-3 的熔断器组合电器,只有在作为没有分断能力的熔断器式隔离器时、在不超过额定绝缘电压使用并进行相应的标识时,才允许超过额定工作电压运行。 | |
所使用熔断器的允许损耗功率: | 3 W |
获取联系人
跳转至联系页面
电话:+86 10 67870300
邮箱:info@woehner.com.cn