订货号 11800000A
CrossBoard®
基座系统 250 A
3 极
800 mm 长,防触摸保护
when fixing on a mounting plate, article 01585 is additionally required
带 CrossLink® 接口
新型
系统
CrossBoard® 125A / 250A
产品优势
touch-safe protected busbar system up to 250 A
rear feedable
plug and play
easy to screw to mounting plates
completely pre-assembled and immediately ready for use
产品组 | 06 |
分组 |
50 |
包装件数 | 1 |
EAN | 4021267118006 |
ECLASS 6.1 | 27400613 |
ECLASS 7.1 | 27400613 |
ETIM 4.0 | EC001900 |
ETIM 5.0 | EC001900 |
标准
IEC 61439-1:2020
UL 508
认证许可
IEC (CB) , UL
for UL feeder circuits >250V
型号: CB-XL-800-24x16
UL 文件: E123577, UL 类别 (适用美国) : NMTR https://www.ul.com
UL 文件: E123577, UL 类别 (适用加拿大) : NMTR7 https://www.ul.com
CCC 认证: 无需强制认证
Details IEC | |
标准 | |
IEC 61439-1:2020 |
Electrical data IEC | |
额定电流(IEC): | 250 A |
额定电压(IEC)AC: | 690 V |
rated isolation voltage Ui AC: | 800 V |
额定冲击耐受电压 Uimp: | 6 kV |
额定冲击耐受电流 Ipk : | 30 kA |
rated short-time withstand current Icw (0.1 s) max.: | 15 kA |
Supplementary data IEC | |
下述参数已经在特定条件下通过测试得到验证。开始设计之前,请联系维纳尔咨询这些条件。 |
最大电压 IEC DC: | 800 V |
Details UL | |
标准 | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
额定电流 (UL): | 250 A |
额定电压 (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
额定电压 (UL) DC: | 600 V |
SCCR unprotected max.: | 10 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
短路电流额定值: |
100 kA with JDDZ fuse Class J 400 A / 600 V AC
65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC |
机械数值 | |
宽 x 高 x 厚: | 800 x 160 x 45 |
重量: | 301.5 kg/100 |
极数: | 3线 |
防护等级: | IP20 |
说明 |
Crossboards before production date November 2024 also suitable for 250 A (IEC + UL). Confirmation |