Inovações
Produtos
A imagem pode mostrar um produto similar.
Código da peça: 33617000A
QUADRON®185Power Speed
chave seccionadora vertical NH tamanho do fusível 00
versão alta, terminais de saída na parte superior M8
conexão por parafuso
para barramentos 30, 40, 60, 80, 100, 120 x 10
not suitable for systems with CrossLink protection modules
Sistema
185Power
Vantagens do produto
When the cover is open, all touchable parts are voltage-free
Operator-independent switching
Lockable cover with double-bit lock
Mixed installation with all components 185Power
Can be sealed when switched on or off
Can be locked with up to 3 padlocks when switched off
Grupo de produto | 18 |
Subgroup | 52 |
Unidade por pacote | 1 |
EAN | 4021267336172 |
ECLASS 6.1 | 27142108 |
ECLASS 7.1 | 27142108 |
ETIM 4.0 | EC001046 |
ETIM 5.0 | EC001046 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
IEC (CB)
Número de tipo: QS185-00
for fuse links size: | NH 000, NH 00 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 12 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Dados IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Dados elétricos IEC | |
Corrente de medição (IEC): | 160 A |
Tensão de medição (IEC) AC: | 800 V |
Tensão de medição (IEC) DC: | 800 V |
Tensão nominal de isolamento: | 1000 V |
rated isolation voltage Ui DC: | 1000 V |
Tensão suportável nominal de impulso Uimp: | 8 kV |
Utilisation category AC (IEC 60947-3) : | AC-22B (800 V / 63 A) |
Utilisation category DC (IEC 60947-3) : | DC-20B max. voltage between the fuses: 1000 V visible information required: Do not switch under load. |
cond. short-circuit current with fuses (AC): | 30 kA / 800 V (63 A) |
100 kA / 690 V | |
120 kA / 500 V | |
approved wth fuse links of operation class: | gG |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 35,2 W.
(A dissipação de energia em sua carga máxima seria 55,0 W.)
Dados adicionais IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
The use of knife links is not permitted. The rated values specified in this product description apply exclusively to the use of fuses. | |
distance to grounded parts = 0mm at 120kA | |
Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals. | |
Degree of protection IP30 at front, degree of protection near terminal depends on installation |
Dados mecânicos | |
L x A x P: | 50 x 773 x 272 |
Peso: | 450,0 kg/100 |
para barramentos: | 30, 40, 60, 80, 100, 120 x 10 |
CT can be integrated in the device: | ja |
front degree of protection: | IP30 |
Type of fastening:
can be screwed onto drilled busbar
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
permitted power dissipation of the fuse-link: | 12 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Encontre sua pessoa de contato
Para a página de contato
Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil
Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de
Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com