Seleção de produtos

for UL feeder circuits >250V

suporte para fusíveis cilíndricos (31555)

A imagem pode mostrar um produto similar.

Descrição

Código da peça: 31555000

SECUR®Panel

suporte para fusíveis cilíndricos

10 x 85 / 1P

32 A, 1500 V DC

für DIN Tragschiene

Sistema

DIN rail

Vantagens do produto

easy replacement of the fuse-link
front degree of protection IP20 always guaranteed

Grupo de produto 17
Subgroup 18
UE 5
EAN 4021267315559
catalog page 2020 : 6.7
ECLASS 6.1 27142190
ECLASS 7.1 27142190
ETIM 4.0 EC002705
ETIM 5.0 EC002705

Aprovações

Standards

IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016

UL 4248-1

UL 4248-19

Approvals

UL

Número de tipo: AES10x85

UL file: E342576, UL category (for USA): IZMR https://www.ul.com

Dados técnicos

for fuse links size: 10x85
fuse links acc. to standard: IEC / EN 60269-6
permitted power dissipation of the fuse-link: 6 W
Dados IEC
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016
Dados elétricos IEC
Corrente de medição (IEC): 32 A
Tensão de medição (IEC) AC: 1000 V
Tensão de medição (IEC) DC: 1500 V
Tensão suportável nominal de impulso Uimp: 8 kV
The insulation performance of the article depends on the installation conditions.

Dissipação de energia do artigo:

A dissipação de energia em uma carga de 80% resulta em 0,2 W.

(A dissipação de energia em sua carga máxima seria 0,3 W.)

Dados adicionais IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

for fuse links 10x85 or 14x85 as per IEC 60269-2, -4, -6
with permitted rated power dissipations up to max. 6.0W
Dados UL
Standards
UL 4248-1
UL 4248-19
Dados electricos UL
rated current (UL): 30 A
rated voltage (UL) DC: 1500 V
SCCR: 15 kA
Dados mecânicos
L x A x P: 22.5 x 130 x 65
Peso: 9,2 kg/100
Polaridade: 1 polo
Mounting: für DIN Tragschiene
front degree of protection: IP20
pontos terminais
cage clamp connection
screw drive: PZ2
wire stripping: 11 mm
min. cross-section: 0,75 mm²
max. cross-section: 25 mm²
Md min.: 2,0 Nm
Md max.: 2,5 Nm
Not suitable for aluminium cables !
  

Box terminal

for applications acc. to IEC / EN :
1 wire:
Cu 0,75 - 25 mm²
2 wires (of same cross-section):
Cu 0,75 - 10 mm²
flexible cables, directly or with wire-end ferrule
(flexible cables of max. cross-section may not fit when using wire-end ferrule)
Md 2,0 - 2,5 Nm / 18 - 22 lb.in.

for applications acc. to UL  :
only stranded Cu cables acc. to UL 486E
1 wire:
AWG 18 - AWG 4
2 wires (of identical cross-section):
AWG 18 - AWG 6
Md 2,0 - 2,5 Nm / 18 - 22 lb.in.

Notas

Min. permitted ambient temperature: -25°C (installation only at temperatures > -5°C)
Climate resistance as per IEC 61439-1, max. pollution degree 3
Please note when inserting the fuse-carrier (with or without fuse-link): insert the fuse-carrier quickly

Links

Downloads

Acessórios

31558000
fusível cilíndrico 25 A
1100 V DC, gPV
14 x 85
Mais

31559000
fusível cilíndrico 20 A
1100 V DC, gPV
14 x 85
Mais

Encontre sua pessoa de contato

Para a página de contato

Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil

Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de

Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com