Innovationen
Prodotti
The picture may show a similar product.
Cod.art.: 01570000A
CRITO®60Classic
Piastra con morsetti di connessione, 3p
10 - 120 mm², AWG 2 - 250 MCM, lam. Cu. 9 - 15,5 x 2,4 - 10
copertura rimovibile soltanto con attrezzo
per barre 12, 15, 20, 25, 30 x 5, 10 e barre profilate
Montaggio
60Classic
Vantaggi prodotto
Terminals can be removed for connection of uncut conductors
gruppo di prodotto | 07 |
sottogruppo prodotto | 45 |
pz/ conf. | 1 |
EAN | 4021267015701 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Norme
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Omologazioni
CSA , UL , DNV GL
for UL feeder circuits >250V
type no.: 243-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
Omologazione CCC : no certification required
Details IEC | |
Norme | |
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
Electrical data IEC | |
corrente nominale (IEC): | 250 A |
tensione nominale (IEC) AC: | 690 V |
tensione di picco Uimp: | 6 kV |
resistenza nom. alla corrente di picco Ipk max.: | 56.3 kA |
Supplementary data IEC | |
I seguenti valori sono stati rilevati tramite prove con determinate condizioni. Prima di progettare vostro impianto chiedere a Wöhner suddette condizioni. |
tensione max. ammissibile (IEC) AC: | 1000 V |
tensione max. ammissibile (IEC) DC: | 1500 V |
corrente d'impiego max. (IEC): | 440 A |
Details UL | |
Norme | |
UL 508 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Electrical data UL | |
corrente nominale (UL): | 255 A |
tensione nominale (UL) AC: | 600 V |
frequenza nominale (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 10 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
SCCR: |
100 kA with JDDZ fuse Class J 500 A / 600 V AC
100 kA with JDDZ fuse Class J 600 A / 480 V AC 35 kA with any DIVQ/7 circuit breaker 600 A / 600 V AC 50 kA with any DIVQ/7 circuit breaker 600 A / 480 V AC 65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC |
Valori meccanici | |
L x A x P: | 81 x 200 x 84 |
peso: | 53,5 kg/100 |
Poli: | 3 poli |
per barre: | 12, 15, 20, 25, 30 x 5, 10 e barre profilate |
Connessioni | |
cage clamp connection | |
wire stripping: | 25 mm |
min. cross-section: | 10 mm² |
max. cross-section: | 150 mm² |
re: | 10 - 10 mm² |
rm: | 16 - 150 mm² |
f: | 16 - 120 mm² |
f + AE: | 10 - 120 mm² |
(f + AE may not fit with max. cross-section) | |
Alveolo di serraggio: | 15 x 15 |
Md min.: | 12,0 Nm |
Md max.: | 12,5 Nm |
Not suitable for aluminium cables ! |
Not suitable for aluminium cables ! | |
La capacità di isolamento dell'articolo dipende dalle condizioni di installazione. | |
for UL feeder circuits >250V |
Trova il tuo contatto
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com