sistema a barre preassemblato 125 A (11405)     PCF: 10,43 kg CO2e

The picture may show a similar product.

Descrizione

Cod.art.: 11405000A

CrossBoard®

sistema a barre preassemblato 125 A

3p

lunghezza 405 mm, protetta contro contatti accidentali

con CrossLink® interface

Montaggio

CrossBoard® 125A / 250A

Vantaggi prodotto

all-round touch-safe protected busbar system up to 125 A
mounting to DIN rails with no tools
simple screwing-on to mounting plates
completely pre-assembled and ready to use

gruppo di prodotto 06
sottogruppo prodotto 50
pz/ conf. 1
EAN 4021267114053
ECLASS 6.1 27400613
ECLASS 7.1 27400613
ETIM 4.0 EC001900
ETIM 5.0 EC001900

Certificazioni

Norme

IEC 61439-1:2020

UL 508

Omologazioni

IEC (CB) , UL

for UL feeder circuits >250V

type no.: CB405-24x7

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

Omologazione CCC : no certification required

Dati tecnici

Details IEC
Norme
IEC 61439-1:2020
Electrical data IEC
corrente nominale (IEC): 125 A
tensione nominale (IEC) AC: 690 V
tensione nominale di isolamento Ui AC: 800 V
tensione di picco Uimp: 6 kV
resistenza nom. alla corrente di picco Ipk max.: 25 kA
corrente nom. di breve durata Icw (0,3 s) max.: 10 kA

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 6,0 W.

(The power dissipation at full load would be 9,3 W.)

Supplementary data IEC

I seguenti valori sono stati rilevati tramite prove con determinate condizioni. Prima di progettare vostro impianto chiedere a Wöhner suddette condizioni.

tensione max. ammissibile (IEC) DC: 800 V
Details UL
Norme
UL 508
for UL feeder circuits >250V
Electrical data UL
corrente nominale (UL): 100 A
tensione nominale (UL) AC: 600 V
frequenza nominale (UL): 50 / 60 Hz
tensione nominale (UL) DC: 600 V
SCCR unprotected max.: 10 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
with JDDZ fuse Class J 175 A / 600 V AC
SCCR: 65 kA with any DIVQ/7 circuit breaker 100 A / 600 V AC
100 kA with any DIVQ/7 circuit breaker 100 A / 480 V AC
100 kA with JDDZ fuse Class J 175 A / 600 V AC
Valori meccanici
L x A x P: 405 x 160 x 45
peso: 137,2 kg/100
Poli: 3 poli
grado di protezione: IP20

Application notes

Avvisi e consigli

We recommend the use of a high DIN rail (35x15) for optimum stability and maximum load of 4 kg.
For higher loads we recommend to fix the CrossBoard® with screws on a panel.
For the use of the QUADRON®CrossBoard NH fuse switch-disconnector size 000 the CrossBoard® has to be fixed with screws on a panel.
For details please see the mounting instruction.

2 CrossBoards® mounted side by side can get a shared feeding component.

The drilling plan for mounting 2 CrossBoards® side by side is available as Dimensioned drawing #2

for UL feeder circuits >250V

Links

Downloads

Accessori

11050000A
CrossBar®
mounting rail for accessories
attachable to CrossBoard
for distribution terminals
NUOVO
Di Più

11051000A
CrossBar®
mounting rail for accessories
attachable to CrossBoard
for distribution blocks
per: Phoenix Contact PTFIX
NUOVO
Di Più

Trova il tuo contatto

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com