Piastra con morsetti di connessione, 3p (01165)

The picture may show a similar product.

Descrizione

Cod.art.: 01165000

CRITO®30Compact

Piastra con morsetti di connessione, 3p

35 - 150 mm², AWG 2 - 300 MCM,  lam. Cu. 15 - 20 x 5 - 10

per barre 12 x 5, 10

Montaggio

30Compact 3P

Vantaggi prodotto

Terminals with captive clamping screws
Conductor can be overlapped
Indication of nominal cross-section and tightening torque noted on the terminals.

gruppo di prodotto 07
sottogruppo prodotto 48
pz/ conf. 1
EAN 4021267011659
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Certificazioni

Norme

IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Omologazioni

UL

for UL feeder circuits >250V

type no.: M150-L

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

Omologazione CCC : no certification required

Dati tecnici

Details IEC
Norme
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
Electrical data IEC
corrente nominale (IEC): 275 A
tensione nominale (IEC) AC: 690 V
resistenza nom. alla corrente di picco Ipk max.: 45.9 kA
Supplementary data IEC

I seguenti valori sono stati rilevati tramite prove con determinate condizioni. Prima di progettare vostro impianto chiedere a Wöhner suddette condizioni.

tensione max. ammissibile (IEC) AC: 1000 V
tensione max. ammissibile (IEC) DC: 1500 V
corrente d'impiego max. (IEC): 480 A
Details UL
Norme
UL 508
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
corrente nominale (UL): 285 A
tensione nominale (UL) AC: 600 V
frequenza nominale (UL): 50 / 60 Hz
SCCR: 18 kA
Valori meccanici
L x A x P: 90 x 160 x 115
peso: 57,5 kg/100
Poli: 3 poli
per barre: 12 x 5, 10
Connessioni
min. cross-section: 35 mm²
max. cross-section: 150 mm²
Not suitable for aluminium cables !
  

for applications acc. to IEC / EN :
35 - 150 mm² stranded round cables and stranded sectored cables
flexible cables, directly or with wire-end ferrule
(flexible cables of maximum cross-section may not fit when using wire-end ferrule)

also for the connection of lam. Cu up to 20x10

for applications acc. to UL / CSA :
only Cu cables Class B acc. to UL 486E
35 - 150 mm² / AWG 2 - MCM 300

Application notes

Not suitable for aluminium cables !
La capacità di isolamento dell'articolo dipende dalle condizioni di installazione.
for UL feeder circuits >250V

Links

Downloads

Trova il tuo contatto

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com