Innovationen
Prodotti
The picture may show a similar product.
Cod.art.: 01135000
CRITO®
Morsetto a pinza
35 - 150 mm², AWG 2 - 300 MCM, lam. Cu. 15 - 20 x 5 - 10
per barre 12, 15, 20 x 5, 10
Montaggio
60Classic, 30Compact 3P
Vantaggi prodotto
Terminal with captive clamping screws, conductor can be overlapped.
Indication of nominal cross-section and tightening torque noted on the terminal.
Contact between conductor and busbar via cable bed.
gruppo di prodotto | 07 |
sottogruppo prodotto | 19 |
pz/ conf. | 6 |
EAN | 4021267011352 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Norme
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Omologazioni
UL
for UL feeder circuits >250V
type no.: 515-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
Omologazione CCC : no certification required
Details IEC | |
Norme | |
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
Electrical data IEC | |
corrente nominale (IEC): | 275 A |
tensione nominale (IEC) AC: | 690 V |
resistenza nom. alla corrente di picco Ipk max.: | 49.8 kA |
Supplementary data IEC | |
I seguenti valori sono stati rilevati tramite prove con determinate condizioni. Prima di progettare vostro impianto chiedere a Wöhner suddette condizioni. |
tensione max. ammissibile (IEC) AC: | 1000 V |
tensione max. ammissibile (IEC) DC: | 1500 V |
corrente d'impiego max. (IEC): | 480 A |
Details UL | |
Norme | |
UL 508 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Electrical data UL | |
corrente nominale (UL): | 285 A |
tensione nominale (UL) AC: | 600 V |
frequenza nominale (UL): | 50 / 60 Hz |
SCCR: | 18 kA |
Valori meccanici | |
L x A x P: | 28 x 34 x 69 |
peso: | 10,2 kg/100 |
per barre: | 12, 15, 20 x 5, 10 |
Connessioni | |
min. cross-section: | 35 mm² |
max. cross-section: | 150 mm² |
Alveolo di serraggio: | 20 x 22 |
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
for applications acc. to IEC / EN : |
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
La capacità di isolamento dell'articolo dipende dalle condizioni di installazione. | |
for UL feeder circuits >250V |
Trova il tuo contatto
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com