Base per fusibili Class J, per barre, connessione in basso /alto (33422)

The picture may show a similar product.

Descrizione

Cod.art.: 33422000

QUADRON®60Classic

Base per fusibili Class J, per barre, connessione in basso /alto

per fusibili Class J, 35 - 60 A (27x60)

3p, con morsetto a gabbia

connessione cavi in alto o basso

per barre 12, 15, 20, 25, 30 x 5, 10 e barre profilate

Montaggio

60Classic

Vantaggi prodotto

the product is based on the UL approval in category IZLT2 also listed in category NMTR (file E123577)

CrossLink® adapter technology
Fast and safe conversion of the connection for top or bottom; the parts under voltage remain shock protected Simple and safe clicking into place and making contact
Safe connection through shock protection split into 2
Busbar supports for flat busbars can be mounted above each other

gruppo di prodotto 16
sottogruppo prodotto 24
pz/ conf. 1
EAN 4021267334222
ECLASS 6.1 27142190
ECLASS 7.1 27142190
ETIM 4.0 EC002705
ETIM 5.0 EC002705

Certificazioni

Norme

IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H

UL 4248-8

UL 4248-1

Omologazioni

UL

for UL feeder circuits >250V

type no.: QCC-ClassJ60A

UL file: E230163, UL category (for USA): IZLT2 https://www.ul.com

UL file 2: E123577, UL category+ (for USA): NMTR https://www.ul.com

UL file: E230163, UL category (for Canada): IZLT8 https://www.ul.com

UL file 2: E123577, UL category+ (for Canada): NMTR7 https://www.ul.com

Dati tecnici

per fusibili di grandezza: Class J 60 A
fusibile secondo norma: UL 248-8
potenza diss. max. ammissibile del fusibile inserito: 7 W
Details IEC
Norme
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H

Valori elettrici

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 2,3 W.

(The power dissipation at full load would be 3,5 W.)

System component: degree of protection IP30 at front as per DIN EN 60529, degree of protection near terminal depends on installation
adapter module: front side degree of protection IP20 as per DIN EN 60529 (finger-safe)
Details UL
Norme
UL 4248-8
UL 4248-1
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
corrente nominale (UL): 60 A
tensione nominale (UL) AC: 600 V
frequenza nominale (UL): 50 / 60 Hz
tensione nominale (UL) DC: 600 V
for wires UL: Cu 75°C
SCCR: 200 kA
Valori meccanici
L x A x P: 106 x 200 x 135
peso: 135,0 kg/100
Poli: 3 poli
per barre: 12, 15, 20, 25, 30 x 5, 10 e barre profilate

Busbar connector: externally tensioned contacting, convenient click mechanism, simple conversion of the combination bases from 5 to 10mm-thick busbars

Connessioni
Not suitable for aluminium cables !
  
min. cross-section UL: AWG 14
max. cross-section UL: AWG 2/0
for wires UL: Cu 75°C
  

AWG 12 - AWG 2/0 stranded, equivalent 3,3 - 67,4 mm²
AWG 14 - AWG 10 solid, equivalent 215 - 5,3 mm²

Application notes

Not suitable for aluminium cables !
potenza diss. max. ammissibile del fusibile inserito: 7 W
for UL feeder circuits >250V

Links

Downloads

Trova il tuo contatto

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com