Cod.art.: 33505000
QUADRON®Panel Speed
Sezionatore sottocarico per fusibili NH, 3p
morsetti a gabbia, per manovra rinviata
Gr. NH 00
double-breaking
operator independent switching (snap-action mechanism)
for mounting plate
Montaggio
Panel
Vantaggi prodotto
With spring-controlled switch mechanism for frequent switching as per utilisation category "A"
FLAG indicator shows the switch setting
Fuses can be changed safely and without tools thanks to double-breaking main contacts
Additional visible separating section by removing the cover incl. fuses
Can be used as mains disconnector as per IEC / EN 60204-1 (main switch)
Also as an Emergency Off switch in combination with the red-yellow door coupling twist handle
Main switch and Emergency Off only in combination with AC-23A/B
Switches can be installed 90° left/right horizontal, always with the same switch lug position
gruppo di prodotto | 15 |
sottogruppo prodotto | 03 |
pz/ conf. | 1 |
EAN | 4021267335052 |
ECLASS 6.1 | 27371401 |
ECLASS 7.1 | 27371401 |
ETIM 4.0 | EC001040 |
ETIM 5.0 | EC001040 |
Norme
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
type no.: QCS-NH00
per fusibili di grandezza: | NH 000, NH 00 |
fusibile secondo norma: | IEC / HD 60269-2 |
potenza diss. max. ammissibile del fusibile inserito: | 10 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Details IEC | |
Norme | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
corrente nominale (IEC): | 125 A |
tensione nominale (IEC) AC: | 690 V |
tensione nominale di isolamento Ui AC: | 800 V |
tensione di picco Uimp: | 8 kV |
Categoria d'impiego AC: | AC-23B (690V/125A) AC-23A (500V/125A) AC-22A (690V/125A) |
Categoria d'impiego DC: | 2 current paths (L1,L3) in series DC-22B (220V/125A) 3 current paths in series DC-22B (440V/63A) |
corrente nom. di cto cto condizionata da fusibili (AC): | 50 kA / 690 V (125A) |
secondo prove fatte con fusibili di caratteristica: | gG |
Fuses gL/gG, size 00, 690V/125A for fuse links IEC 60269-2 / DIN VDE 0636-2 size 00 up to 10W power dissipation | |
Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals. | |
When several devices are used side-by-side in continuous operation, the rated load factor specified in VDE 0660 Part 500 / EN 60 439-1, Table 1, must be observed. | |
System component: degree of protection IP20 at front as per DIN EN 60529, dependent upon installation in the connection area; shock protection to DIN EN 50274 |
Valori meccanici | |
L x A x P: | 106 x 233 x 153 |
peso: | 201,6 kg/100 |
Poli: | 3 poli |
Mounting: | for mounting plate |
Connessioni | |
Not suitable for aluminium cables ! | |
Box terminal: |
Not suitable for aluminium cables ! | |
potenza diss. max. ammissibile del fusibile inserito: | 10 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |