Sezionatore sottocarico per fusibili NH, 3p (33501)

The picture may show a similar product.

Descrizione

Cod.art.: 33501000

QUADRON®60Classic Speed

Sezionatore sottocarico per fusibili NH, 3p

morsetti a gabbia, connessione in alto

Gr. NH 00

double-breaking

operator independent switching (snap-action mechanism)

per barre 12, 15, 20, 25, 30 x 5, 10 e barre profilate

Montaggio

60Classic

Vantaggi prodotto

With spring-controlled switch mechanism for frequent switching as per utilisation category "A"
Can be locked in neutral position with up to 3 Upadlocks
FLAG indicator shows the switch setting
Fuses can be changed safely and without tools thanks to double-breaking main contacts
Additional visible separating section by removing the cover incl. fuses
Can be used as mains disconnector as per IEC / EN 60204-1 (main switch).
Mains switch only in combination with AC-23A/B

CrossLink® adapter technology
Simple and safe clicking into place and making contact
Busbar supports can be mounted above each other for flat rails

Compact dimensions (106mm wide)

gruppo di prodotto 15
sottogruppo prodotto 20
pz/ conf. 1
EAN 4021267335014
ECLASS 6.1 27371401
ECLASS 7.1 27371401
ETIM 4.0 EC001040
ETIM 5.0 EC001040

Certificazioni

Norme

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

Omologazioni

IEC (CB) , VDE , CCC , DNV GL

type no.: QCS-NH00

CCC certificate: 2010010302392782

Dati tecnici

per fusibili di grandezza: NH 000, NH 00
fusibile secondo norma: IEC / HD 60269-2
potenza diss. max. ammissibile del fusibile inserito: 10 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Details IEC
Norme
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
corrente nominale (IEC): 125 A
tensione nominale (IEC) AC: 690 V
tensione nominale di isolamento Ui AC: 800 V
tensione di picco Uimp: 8 kV
Categoria d'impiego AC: AC-23B (690V/125A)
AC-23A (500V/125A)
AC-22A (690V/125A)
Categoria d'impiego DC: DC specifications: 2 current paths (L1,L3) in series
DC-22B (220V/125A)
corrente nom. di cto cto condizionata da fusibili (AC): 50 kA / 690 V (125A)
secondo prove fatte con fusibili di caratteristica: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 17,2 W.

(The power dissipation at full load would be 26,8 W.)

Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals.
When several devices are used side-by-side in continuous operation, the rated load factor specified in VDE 0660 Part 500 / EN 60 439-1, Table 1, must be observed.
System component: degree of protection IP20 at front as per DIN EN 60529, degree of protection near terminal depends on installation; shock protection as per DIN EN 50274

adapter module: front side degree of protection IP20 as per DIN EN 60529 (finger-safe)
Valori meccanici
L x A x P: 106 x 200 x 128
peso: 219,0 kg/100
Poli: 3 poli
per barre: 12, 15, 20, 25, 30 x 5, 10 e barre profilate

Busbar connector: externally tensioned contacting, convenient click mechanism, simple conversion of the combination bases from 5 to 10mm-thick busbars

Connessioni
Not suitable for aluminium cables !
  

Box terminal:
1.5 -70mm² flexible cables, directly or with wire-end ferrules*, depending on contour of the insulated lead 95mm² could be connectable
1.5 - 10mm² solid round
16 - 70mm² stranded round
2x10mm², 2x16mm² and 2x25mm² flexible with wire-end ferrules, identical cables placed side by side, crimping square
2x10 - 2x35mm² flexible, identical cables placed side by side square

lam. Cu. 9-13 mm wide
Terminal space 13mm x 13mm

(*flexible cables of maximum cross-section may not fit when using wire-end ferrule)

Application notes

Not suitable for aluminium cables !
potenza diss. max. ammissibile del fusibile inserito: 10 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.

Links

Downloads

Accessori

33908000
microswitch di segnalazione posizione maniglia
contatto di commutazione 250 V AC / 5 A, 30 V DC / 4 A
per: QCS-NH00, QCS-NH1, QCS-160, QCS-320
Di Più

33914000
morsetto 120 mm²
connessione frontale
per: QCS-NH00, QCS-160
Di Più

Trova il tuo contatto

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com