Innovationen
Prodotti
The picture may show a similar product.
Cod.art.: 32412000
EQUES®60Classic
Adattatore 45 A
con 2 guide DIN scorrevoli
54 x 200, parte frontale estraibile, con cavi AWG 8 (10mm²)
per barre 12, 15, 20, 25, 30 x 5, 10 e barre profilate
con CrossLink®Technology
Montaggio
60Classic
Vantaggi prodotto
Conductor ends ultrasonically sealed.
Click mechanism when pushing onto the busbar.
gruppo di prodotto | 05 |
sottogruppo prodotto | 22 |
pz/ conf. | 4 |
EAN | 4021267324124 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Norme
IEC 61439-1:2020
UL 508
Omologazioni
CSA , UL , DNV GL
for UL feeder circuits >250V
type no.: EMC6045-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
Omologazione CCC : no certification required
Details IEC | |
Norme | |
IEC 61439-1:2020 |
Electrical data IEC | |
corrente nominale (IEC): | 45 A |
tensione nominale (IEC) AC: | 690 V |
tensione nominale di isolamento Ui AC: | 800 V |
tensione di picco Uimp: | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 3,5 W.
(The power dissipation at full load would be 5,5 W.)
Details UL | |
Norme | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
corrente nominale (UL): | 45 A |
tensione nominale (UL) AC: | 600 V |
frequenza nominale (UL): | 50 / 60 Hz |
SCCR protected max.: | 65 kA |
SCCR: | 65kA with any DIVQ/7 circuit breaker 40A / 480V AC |
Valori meccanici | |
L x A x P: | 54 x 200 x 75 |
peso: | 52,9 kg/100 |
Poli: | 3 poli |
per barre: | 12, 15, 20, 25, 30 x 5, 10 e barre profilate |
There must be a clearance of at least 12 mm above the article to remove it from the busbar system. | |
Avvisi e consigli |
For compact mounting of complete motor circuits with commercially available switchgear and safe mechanical and electrical connection to the busbar system. In the test position, the structure locks and disconnects safely from the primary energy supply. |
short-circuit withstandability: | the short-circuit capacity of the combination of adapter and motor starter depends on the motor starter |
for UL feeder circuits >250V |
Trova il tuo contatto
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com