Innovazioni
Prodotti
for UL feeder circuits >250V
The picture may show a similar product.
Cod.art.: 32694000A
EQUES®30Compact
Adattatore EEC 30 A
per Siemens S0, con morsetti a molla
45 x 160, con cavi AWG 10 (6 mm²)
per barre 12 x 5, 10
NUOVO
Montaggio
30Compact 3P
Vantaggi prodotto
Conductor ends ultrasonically sealed.
Click mechanism when pushing onto the busbar.
gruppo di prodotto | 05 |
sottogruppo prodotto | 21 |
pz/ conf. | 4 |
EAN | 4021267326944 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Norme
IEC 61439-1:2020
UL 508
Omologazioni
CSA , UL , DNV GL
for UL feeder circuits >250V
type no.: EEC6025C-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
Omologazione CCC : no certification required
Details IEC | |
Norme | |
IEC 61439-1:2020 |
Electrical data IEC | |
corrente nominale (IEC): | 30 A |
tensione nominale (IEC) AC: | 690 V |
tensione nominale di isolamento Ui AC: | 800 V |
tensione di picco Uimp: | 6 kV |
Motorschutzschalter bis 25 A: |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 1.6 W.
(The power dissipation at full load would be 2.5 W.)
Details UL | |
Norme | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
corrente nominale (UL): | 30 A |
tensione nominale (UL) AC: | 600 V |
frequenza nominale (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 5 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 65 kA |
SCCR: |
65 kA with any NKJH Comb. Motor Controller 16 A / 480 V AC
65 kA with any NKJH Comb. Motor Controller 25 A / 480 V AC 30 kA with any NKJH Comb. Motor Controller 12,5 A / 600 V AC 50 kA with any NKJH Comb. Motor Controller 32 A / 480 V AC |
Valori meccanici | |
L x A x P: | 45 x 160 x 63 |
peso: | 19.8 kg/100 |
Poli: | 3 poli |
per barre: | 12 x 5, 10 |
Avvisi e consigli |
For compact mounting of complete motor circuits with commercially available switchgear and safe mechanical and electrical connection to the busbar system. |
short-circuit withstandability: | the short-circuit capacity of the combination of adapter and motor starter depends on the motor starter |
for UL feeder circuits >250V |
Trova il tuo contatto
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com