L'Entreprise
Innovationen
Produits
The picture may show a similar product.
Référence 01070000
CRITO®
bornes à pince
600 - 1200 mm²
bornier 68 x 28
pour jeux de barres 30 x 10 et barres profilées
Système
60Classic, centre feed unit, 100Energy
Avantages produit
also rigid copper busbars can be connected if they are installed without mechnical tension
Groupe de produits | 07 |
Sous-groupe | 30 |
Dimensions de l'emballage | 3 |
EAN | 4021267010706 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Normes
IEC 61439-1:2020
UL 508
Approbations
UL
for UL feeder circuits >250V
Type: CPC63-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
Homologation CCC: no certification required
Details IEC | |
Normes | |
IEC 61439-1:2020 |
Electrical data IEC | |
Courant assigné (IEC): | 1600 A |
Tension assignée (IEC) CA: | 690 V |
rated peak withstand current Ipk max.: | 80 kA |
Supplementary data IEC | |
Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire. |
Tension maximale IEC CA: | 1000 V |
Tension maximale IEC CC: | 1500 V |
Tenue au courant avec alimentation au milieu: | 2 000 A |
Details UL | |
Normes | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 1400 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 30 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 200 kA |
SCCR: |
200 kA with fuse Class L 1600 A
65 kA with any DIVQ/7 circuit breaker 1600 A / 480 V AC/DC |
Charactéristiques mécaniques | |
L x H x P: | 85 x 52 x 87 |
Poids: | 63,0 kg/100 |
pour jeux de barres: | 30 x 10 et barres profilées |
Points de raccordement | |
min. cross-section: | 500 mm² |
max. cross-section: | 1 260 mm² |
Alvéole de serrage: | 68 x 10 - 28 |
Not suitable for aluminium cables ! |
Not suitable for aluminium cables ! | |
Les performances d'isolation de l'article dépendent des conditions d'installation. | |
for UL feeder circuits >250V |
Trouver votre contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com