L'Entreprise
Innovations
Produits
for UL feeder circuits >250V
The picture may show a similar product.
Référence 01318 000
CRITO®
bornes à pince
Cu / Al 95 - 185 mm²
pour jeux de barres 20, 25, 30 x 5, 10 et barres profilées
Système
60Classic, centre feed unit, 100Energy
Avantages produit
Terminal with captive clamp screws, conductor can be overlapped, indication of nominal cross-section and tightening torque noted on the terminal, contact between conductor and busbar via cable bed.
| Groupe de produits | 07 |
| Sous-groupe | 20 |
| Dimensions de l'emballage | 6 |
| EAN | 4021267013189 |
| ECLASS 6.1 | 27141146 |
| ECLASS 7.1 | 27141146 |
| ETIM 4.0 | EC000001 |
| ETIM 5.0 | EC000001 |
Normes
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Approbations
UL
Type: 518
UL file: E123577, UL category (for USA): NMTR2 https://www.ul.com
Homologation CCC: no certification required
| Details IEC | |
| Normes | |
|
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
| Electrical data IEC | |
| Courant assigné (IEC): | 300 A |
| Tension assignée (IEC) CA: | 690 V |
| rated peak withstand current Ipk max.: | 55.8 kA |
| Supplementary data IEC | |
|
Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire. |
| Tension maximale IEC CA: | 1000 V |
| Tension maximale IEC CC: | 1500 V |
| current capacity (IEC) max.: | 500 A |
| Details UL | |
| Normes | |
| UL 508 |
| suitable for field-installed conductors |
| Electrical data UL | |
| rated current (UL): | 310 A |
| rated voltage (UL) AC: | 600 V |
| rated frequency (UL): | 50 / 60 Hz |
| Icc: | 25 kA |
| Charactéristiques mécaniques | |
| L x H x P: | 38 x 51 x 70 |
| Poids: | 31,2 kg/100 |
| pour jeux de barres: | 20, 25, 30 x 5, 10 et barres profilées |
| Points de raccordement | |
| min. cross-section: | 95 mm² |
| max. cross-section: | 185 mm² |
| Md min.: | 24,0 Nm |
| Md max.: | 36,0 Nm |
|
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
|
for applications acc. to IEC / EN : |
|
| Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
| Les performances d'isolation de l'article dépendent des conditions d'installation. | |
|
CSA certificate on request |
|
Trouver votre contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com