Sélection des produits

for UL feeder circuits >250V

bornes à pince (01135)

The picture may show a similar product.

Description

Référence 01135000

CRITO®

bornes à pince

35 - 150 mm², AWG 2 - 300 MCM,  lam. Cu. 15 - 20 x 5 - 10

pour jeux de barres 12, 15, 20 x 5, 10

Système

60Classic, 30Compact 3P

Avantages produit

Terminal with captive clamping screws, conductor can be overlapped.
Indication of nominal cross-section and tightening torque noted on the terminal.
Contact between conductor and busbar via cable bed.

Groupe de produits 07
Sous-groupe 19
Dimensions de l'emballage 6
EAN 4021267011352
catalog page 2020 : 2.2, 3.6
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Homologations

Normes

IEC 61439-1:2011
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Approbations

UL , EAC

for UL feeder circuits >250V

Type: 515-L

EAC Type: TE-B

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

Homologation CCC: no certification required

Données techniques

Details IEC
Normes
IEC 61439-1:2011
IEC 60999-1:1999
IEC 60999-2:2003
Electrical data IEC
Courant assigné (IEC): 275 A
Tension assignée (IEC) CA: 690 V
Les performances d'isolation de l'article dépendent des conditions d'installation.
rated peak withstand current  Ipk max.: 49.8 kA
Supplementary data IEC

Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire.

Tension maximale IEC CA: 1000 V
Tension maximale IEC CC: 1500 V
current capacity (IEC) max.: 480 A
Details UL
Normes
UL 508
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
rated current (UL): 285 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
Icc: 18 kA
Charactéristiques mécaniques
L x H x P: 28 x 34 x 69
Poids: 10,2 kg/100
pour jeux de barres: 12, 15, 20 x 5, 10
Points de raccordement
min. cross-section: 35 mm²
max. cross-section: 150 mm²
Alvéole de serrage: 20 x 22
Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
  

for applications acc. to IEC / EN :
Cu or Al 35 - 150 mm² stranded round cables and stranded sectored cables
Cu also flexible cables, directly or with wire-end ferrule
(flexible cables of maximum cross-section may not fit when using wire-end ferrule)

for applications acc. to UL / CSA :
Cu 35 - 150 mm² / AWG 2 - MCM 300

Conseils

Connections not maintenance-free if aluminium conductors are used (also see catalogue 8.2)

Links

Documentation

Trouver votre contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Produits Configurateur Calcul de la plus-value métal folder for files