support pour fusibles cylindriques

The picture may show a similar product.

Description

Référence 31118 200

AMBUS Panel

support pour fusibles cylindriques

for mounting rail

Difference:Großverpackung

Système

Panel

Groupe de produits 17
Sous-groupe 09
Dimensions de l'emballage 56
EAN 4021267151218
ETIM 5.0 EC002705
ETIM 8.0 EC002705

Homologations

Normes

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

UL 4248-1

Approbations

CSA , UL , CCC

for UL feeder circuits >250V

Type: AES14x51

EAC Type: AES

UL file: E230163, UL category (for USA): IZLT https://www.ul.com

UL file: E230163, UL category (for Canada): IZLT7 https://www.ul.com

CCC certificate: 2004010302117255

Données techniques

for fuse links size: 14x51
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 5 W
Details IEC
Normes
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
Courant assigné (IEC): 50 A
Tension assignée (IEC) CA: 690 V
rated isolation voltage Ui AC: 800 V
Tension assignée de tenue aux chocs Uimp: 6 kV
cond. short-circuit current with fuses (AC): 100 kA / 400 V (50 A)
100 kA / 500 V (40 A)
80 kA / 690 V (25 A)
approved wth fuse links of operation class: gG
Supplementary data IEC

Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire.

Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence.
min. permitted operation temperature -40°C
Details UL
Normes
UL 4248-1
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
rated current (UL): 50 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
rated voltage (UL) DC: 600 V
for wires UL: Cu 75°C
Icc: 100 kA
Charactéristiques mécaniques
L x H x P: 81 x 90 x 69
Poids: 30,4 kg/100
Pôles: 3 pôles
Mounting: for mounting rail
degree of protection: IP20
front degree of protection: IP20
Points de raccordement
cage clamp connection
screw drive: PZ2
wire stripping: 14 mm
min. cross-section: 1,5 mm²
max. cross-section: 35 mm²
Md min.: 2,5 Nm
Md max.: 3,0 Nm
Not suitable for aluminium cables !
  
min. cross-section UL: AWG 14
max. cross-section UL: AWG 2
torque (UL): 26 lb-in
for wires UL: Cu 75°C
Charactéristiques des matériaux
halogen-free: Yes

Application notes

Not suitable for aluminium cables !
Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence.
permitted power dissipation of the fuse-link: 5 W
for UL feeder circuits >250V