L'Entreprise
Innovationen
Produits
The picture may show a similar product.
Référence 01570000A
CRITO®60Classic
plaque bornier, 3 pôles
10 - 120 mm², AWG 2 - 250 MCM, lam. Cu. 9 - 15,5 x 2,4 - 10
le cache peut uniquement être retiré à l'aide d'un outil
pour jeux de barres 12, 15, 20, 25, 30 x 5, 10 et barres profilées
Système
60Classic
Avantages produit
Terminals can be removed for connection of uncut conductors
Groupe de produits | 07 |
Sous-groupe | 45 |
Dimensions de l'emballage | 1 |
EAN | 4021267015701 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Normes
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Approbations
CSA , UL , DNV GL
for UL feeder circuits >250V
Type: 243-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
Homologation CCC: no certification required
Details IEC | |
Normes | |
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
Electrical data IEC | |
Courant assigné (IEC): | 250 A |
Tension assignée (IEC) CA: | 690 V |
Tension assignée de tenue aux chocs Uimp: | 6 kV |
rated peak withstand current Ipk max.: | 56.3 kA |
Supplementary data IEC | |
Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire. |
Tension maximale IEC CA: | 1000 V |
Tension maximale IEC CC: | 1500 V |
current capacity (IEC) max.: | 440 A |
Details UL | |
Normes | |
UL 508 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Electrical data UL | |
rated current (UL): | 255 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 10 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
SCCR: |
100 kA with JDDZ fuse Class J 500 A / 600 V AC
100 kA with JDDZ fuse Class J 600 A / 480 V AC 35 kA with any DIVQ/7 circuit breaker 600 A / 600 V AC 50 kA with any DIVQ/7 circuit breaker 600 A / 480 V AC 65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC |
Charactéristiques mécaniques | |
L x H x P: | 81 x 200 x 84 |
Poids: | 53,5 kg/100 |
Pôles: | 3 pôles |
pour jeux de barres: | 12, 15, 20, 25, 30 x 5, 10 et barres profilées |
Points de raccordement | |
cage clamp connection | |
wire stripping: | 25 mm |
min. cross-section: | 10 mm² |
max. cross-section: | 150 mm² |
re: | 10 - 10 mm² |
rm: | 16 - 150 mm² |
f: | 16 - 120 mm² |
f + AE: | 10 - 120 mm² |
(f + AE may not fit with max. cross-section) | |
Alvéole de serrage: | 15 x 15 |
Md min.: | 12,0 Nm |
Md max.: | 12,5 Nm |
Not suitable for aluminium cables ! |
Not suitable for aluminium cables ! | |
Les performances d'isolation de l'article dépendent des conditions d'installation. | |
for UL feeder circuits >250V |
Trouver votre contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com