Sélection des produits

for UL feeder circuits >250V

alimentation en tension 10 A (36200000A)

The picture may show a similar product.

Description

Référence 36200 000A

BROOME10 CrossBoard

alimentation en tension 10 A

400 V AC / 24 V DC, avec bornes à ressort

avec interface CrossLink

Système

CrossBoard 125A / 250A, CrossBoard 800 A

Avantages produit

Direct installation to CrossBoard®
Efficiency of 95% permits an installation width of 45 mm
Self-protected at short-circuit with intelligent re-start
No pre-fuse needed
Overvoltage category III

Groupe de produits 21
Sous-groupe 40
Dimensions de l'emballage 1
EAN 4021267362003
ECLASS 14.0 27142325
ETIM 5.0 EC002540
ETIM 8.0 EC002540
ETIM 10.0 EC002540

Homologations

Normes

IEC 61010-1:2010
IEC 61010-2-201:2013

UL 61010-1

UL 61010-2-201

Approbations

IEC (CB) , UL

for UL feeder circuits >250V

Type: BROOME10

EAC Type: PS

UL file: E497002, UL category (for USA): NMTR. https://www.ul.com

UL file: E497002, UL category (for Canada): NMTR7. https://www.ul.com

Données techniques

Details IEC
Normes
IEC 61010-1:2010
IEC 61010-2-201:2013
Electrical data IEC
Tension assignée (IEC) CA: 480 V
min. operating voltage AC: 380 V
output voltage DC: 24 V
output current: 10 A
voltage control: No
typical hold-up time (400 V): 20 ms
typical hold-up time (480 V): 20 ms
separation input / output: SELV / PELV
over-voltage protection: 32 V
parallel operation possible: Yes
serial operation possible: Yes
rated frequency (IEC): 50 / 60 Hz
rated isolation voltage Ui AC: 500 V
Tension assignée de tenue aux chocs Uimp: 4 kV

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 8,2 W.

(The power dissipation at full load would be 12,8 W.)

Supplementary data IEC

Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire.

min. permitted operation temperature -25°C
max. permitted operation temperature 70°C
min. permitted temperature for transport and storage -25°C
max. permitted temperature for transport and storage 70°C
2-pole feeding at L1 and L2
Details UL
Normes
UL 61010-1
UL 61010-2-201
for UL feeder circuits >250V
Electrical data UL
rated voltage (UL) AC: 480 V
min. operating voltage AC: 380 V
rated frequency (UL): 50 / 60 Hz
Charactéristiques mécaniques
L x H x P: 45 x 160 x 130
Poids: 71,8 kg/100
Pôles: 2 pôles
degree of protection: IP30
for vertical busbar system: Yes
for horizontal busbar system: No
Points de raccordement
push-in connection
AWG14 (2,5 mm²)
screw drive: 0.5x3
wire stripping: 10 mm
min. cross-section: 0,2 mm²
max. cross-section: 2,5 mm²
  
min. cross-section UL: AWG 24
max. cross-section UL: AWG14
  

f+AE max. 1,5 mm²

Charactéristiques des matériaux
halogen-free: Yes

Application notes

for UL feeder circuits >250V

Links (Prices, CAD data)

Documentation

Trouver votre contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com