L'Entreprise
Innovations
Produits
The picture may show a similar product.
Référence 32749000A
EQUES®185Power
adaptateur de jeu de barres, 1150 A
300 x 652, rotation de phase
raccordement à l'adaptateur par le bas
for systems with drilled busbars
pour Siemens 3VL7 (1250 A)
pour jeux de barres 30, 40, 60, 80, 100, 120 x 10
not suitable for systems with CrossLink protection modules
Produit en fin de vie
Système
185Power
Groupe de produits | 05 |
Sous-groupe | 48 |
Dimensions de l'emballage | 1 |
EAN | 4021267327491 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Normes
IEC 61439-1:2020
UL 508
Approbations
UL
for UL feeder circuits >250V
Type: EQ185-A1600-S
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
Homologation CCC: no certification required
Details IEC | |
Normes | |
IEC 61439-1:2020 |
Electrical data IEC | |
Courant assigné (IEC): | 1150 A |
Tension assignée (IEC) CA: | 690 V |
Tension assignée (IEC) CC: | 800 V |
rated isolation voltage Ui AC: | 1000 V |
rated isolation voltage Ui DC: | 1000 V |
Tension assignée de tenue aux chocs Uimp: | 12 kV |
rated peak withstand current Ipk max.: | 106 kA |
rated short-time withstand current Icw (1.0 s) max.: | 50 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 166,4 W.
(The power dissipation at full load would be 260,0 W.)
mit Siemens 3VL7 1250A bis 1150A einsetzbar! |
Details UL | |
Normes | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 1200 A |
rated voltage (UL) AC: | 1000 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 50 kA |
3 cycles (without OPD) @ 1000 V AC |
Charactéristiques mécaniques | |
L x H x P: | 300 x 652 x 83 |
Poids: | 3172,0 kg/100 |
Pôles: | 3 pôles |
pour jeux de barres: | 30, 40, 60, 80, 100, 120 x 10 |
Mounting: | for systems with drilled busbars |
CT can be integrated in the device: | ja |
Conseils |
Ausreichend Platz für 2x3 Stromwandler vorhanden. |
short-circuit withstandability: | the short-circuit capacity of the combination of adapter and MCCB depends on the MCCB |
for UL feeder circuits >250V |