Innovationen
Productos
for UL feeder circuits >250V
La imagen puede mostrar un producto similar.
Part No.: 01593000A
CRITO®CrossBoard
módulo de conexión
con terminales tipo brida 6 - 50 mm² / AWG 10 - AWG 1
3 polos
sistema
CrossBoard® 125A / 250A
ventajas del producto
direct connection to the CrossBoard, cover included
capable of feeding (up to 125 A) 1 or 2 CrossBoards simultaneously with balanced or unbalanced load on the boards.
can be used without cables as a bridge connection between 2 CrossBoards up to 125 A. Feeding a third CrossBoard with cables is acceptable, but the total current cannot exceed 125 A.
touch-safe
CRITO® unlockable from top or bottom
grupo de producto | 07 |
subgrupo | 42 |
embalaje | 1 |
EAN | 4021267015930 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Normas
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
homologaciónes
UL
for UL feeder circuits >250V
tipo: CR45-A
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
Homologación CCC: no es obligatoria la certificación
datos IEC | |
Normas | |
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
datos electricos IEC | |
intensidad de corriente nominal (IEC): | 125 A |
tensión nominal (IEC) AC: | 690 V |
tensión nominal de aislamiento Ui AC: | 800 V |
resistencia a corriente de pico Ipk máx. : | 15 kA |
datos adicionales IEC | |
Los siguientes valores han sido verificados con los test bajo ciertas condiciones. Por favor, pregunte a Wöhner por estas condiciones antes de diseñar su cuadro. |
tensión máxima (IEC) AC: | 800 V |
tensión máxima (IEC) DC: | 800 V |
máxima intensidad de corriente (IEC): | 125 A |
datos UL | |
Normas | |
UL 508 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
datos electricos UL | |
intensidad de corriente nominal (UL): | 100 A |
tensión nominal (UL) AC: | 600 V |
frecuencia nominal (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 10 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
SCCR: |
65 kA with any DIVQ/7 circuit breaker 100 A / 600 V AC
100 kA with any DIVQ/7 circuit breaker 100 A / 480 V AC 100 kA with JDDZ fuse Class J 175 A / 600 V AC |
datos mecánicos | |
An x A x P: | 45 x 160 x 92 |
peso: | 25.0 kg/100 |
Polaridad: | 3 polos |
grado de protección frontal: | IP20 |
puntos de apriete | |
cage clamp connection | |
screw drive: | S4 |
wire stripping: | 17 mm |
min. cross-section: | 6 mm² |
max. cross-section: | 50 mm² |
Md min.: | 5.0 Nm |
Md max.: | 6.0 Nm |
min. cross-section UL: | AWG 10 |
max. cross-section UL: | AWG 1/0 |
torque (UL): | 44 - 53 lb-in |
6 - 50 mm² / AWG 10 - AWG 1 (feindrähtig mit Aderendhülse eventuell nicht mit maximalen Querschnitt möglich) |
La capacidad de aislamiento del artículo depende de las condiciones de la instalación. | |
for UL feeder circuits >250V |
Busca tu contacto
a la pagina de contactos
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com