borne en pinza (01135)

La imagen puede mostrar un producto similar.

Descripción

Part No.: 01135000

CRITO®

borne en pinza

35 - 150 mm², AWG 2 - 300 MCM,  lam. Cu. 15 - 20 x 5 - 10

para barras 12, 15, 20 x 5, 10

sistema

60Classic, 30Compact 3P

ventajas del producto

Terminal with captive clamping screws, conductor can be overlapped.
Indication of nominal cross-section and tightening torque noted on the terminal.
Contact between conductor and busbar via cable bed.

grupo de producto 07
subgrupo 19
embalaje 6
EAN 4021267011352
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Homologaciónes

Normas

IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

homologaciónes

UL

for UL feeder circuits >250V

tipo: 515-L

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

Homologación CCC: no es obligatoria la certificación

Datos técnicos

datos IEC
Normas
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
datos electricos IEC
intensidad de corriente nominal (IEC): 275 A
tensión nominal (IEC) AC: 690 V
resistencia a corriente de pico Ipk máx. : 49.8 kA
datos adicionales IEC

Los siguientes valores han sido verificados con los test bajo ciertas condiciones. Por favor, pregunte a Wöhner por estas condiciones antes de diseñar su cuadro.

tensión máxima (IEC) AC: 1000 V
tensión máxima (IEC) DC: 1500 V
máxima intensidad de corriente (IEC): 480 A
datos UL
Normas
UL 508
for UL feeder circuits >250V
suitable for field-installed conductors
datos electricos UL
intensidad de corriente nominal (UL): 285 A
tensión nominal (UL) AC: 600 V
frecuencia nominal (UL): 50 / 60 Hz
SCCR: 18 kA
datos mecánicos
An x A x P: 28 x 34 x 69
peso: 10.2 kg/100
para barras: 12, 15, 20 x 5, 10
puntos de apriete
min. cross-section: 35 mm²
max. cross-section: 150 mm²
Espacio de apriete: 20 x 22
Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
  

for applications acc. to IEC / EN :
Cu or Al 35 - 150 mm² stranded round cables and stranded sectored cables
Cu also flexible cables, directly or with wire-end ferrule
(flexible cables of maximum cross-section may not fit when using wire-end ferrule)

for applications acc. to UL / CSA :
Cu 35 - 150 mm² / AWG 2 - MCM 300

Application notes

Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
La capacidad de aislamiento del artículo depende de las condiciones de la instalación.
for UL feeder circuits >250V

Links

Downloads

Busca tu contacto

a la pagina de contactos

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com