Company
Innovationen
Products
The picture may show a similar product.
Part No.: 01484000
connection busbar support
3-pole, with integrated terminals 1.5 - 16 mm²
for busbars 12, 15, 20, 25, 30 x 5, 10
System
60Classic
Advantages of the product
Connection busbar support with integrated terminals for feeding or tapping the busbar
with internal screw holes, can also be used as centre support.
Product group | 06 |
Subgroup | 09 |
pack size | 10 |
EAN | 4021267014841 |
ECLASS 6.1 | 27400607 |
ECLASS 7.1 | 27400607 |
ETIM 4.0 | EC001166 |
ETIM 5.0 | EC001166 |
Standards
IEC 61439-1:2020
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
rated current (IEC): | 63 A |
rated voltage (IEC) AC: | 690 V |
rated frequency (IEC): | 50 / 60 Hz |
rated isolation voltage Ui AC: | 800 V |
rated surge voltage Uimp : | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 0.5 W.
(The power dissipation at full load would be 0.8 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
current capacity (IEC) max.: | 80 A |
Current capacity of the clamping point 80A short-circuit withstand rating: surge current strength > 30kA at busbar support separation of 550mm surge current strength > 50kA at busbar support separation of 250mm further values in the short-circuit withstand rating diagram |
Mechanical data | |
W x H x D: | 20 x 200 x 87 |
weight: | 25.6 kg/100 |
poles: | 3-pole |
for busbars: | 12, 15, 20, 25, 30 x 5, 10 |
The insulation performance of the article depends on the installation conditions. | |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com