            Company
            
        
        
            Innovations
            
        
        
      
        
            Products
            
        
      	
        
        
        
    The picture may show a similar product.
Part No.: 01620 000
busbar 20 x 5
material: copper Cu-ETP (No. CW004A) acc. to EN 13601 (99.9% copper), strength class R300 (300 N/mm²)
length 2.40 m, tinned
System
60Classic
Advantages of the product
Tin-plated Cu busbars considerably reduce the effort of preparing the contact points.
The Cu busbars are effective protected against aggressive media.
| Product group | 06 | 
| Subgroup | 82 | 
| pack size | 1 | 
| EAN | 4021267016203 | 
| ECLASS 6.1 | 27370303 | 
| ECLASS 7.1 | 27370303 | 
| ETIM 4.0 | EC001522 | 
| ETIM 5.0 | EC001522 | 
Standards
IEC 61439-1:2020
UL 508
Approvals
CSA , UL
																		 
																		 
for UL feeder circuits >250V
type number: 20x5-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
CCC approval: no certification required
| Details IEC | |
| Standards | |
| IEC 61439-1:2020 | 
Electrical data
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 30.7 W.
(The power dissipation at full load would be 48.0 W.)
| Supplementary data IEC | |
| The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. | 
| current at 30 K: | 320 A | 
| Details UL | |
| Standards | |
| UL 508 | 
| for UL feeder circuits >250V | 
| certified in the Woehner UL file E197039 | |
| current rating acc. to UL 508: | 362 A | 
| Notice the rated voltage of the used busbar support in the application. | |
| Mechanical data | |
| W x H x D: | 2400 x 20 x 5 | 
| weight: | 214.4 kg/100 | 
| cross-section: | 100 mm² | 
Edge radius 0.5
| Please respect the insulation characteristics of the busbar support for your application. | |
| see product description of the used busbar support | |
| for UL feeder circuits >250V | 
 
						
                01244
        000
        
        
            busbar cover
            
            
            for 12 - 30 x 5 busbar, 1 m long
            touch protection cover
            
        More
        
						
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com