Company
Innovationen
Products
The picture may show a similar product.
Part No.: 32570000
EQUES®60Classic
busbar adapter 160 A, 3-pole
92 x 200
connection to the system top or bottom
for Eaton NZM1
for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars
with CrossLink®Technology
System
60Classic
Product group | 05 |
Subgroup | 30 |
pack size | 1 |
EAN | 4021267325701 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Standards
IEC 61439-1:2020
UL 508
Approvals
UL
for UL feeder circuits >250V
type number: ECL60160-L
UL file: E353754, UL category (for USA): DHWZ https://www.ul.com
UL file: E353754, UL category (for Canada): DIHS7 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
rated current (IEC): | 160 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 800 V |
rated surge voltage Uimp : | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 11.3 W.
(The power dissipation at full load would be 17.7 W.)
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 160 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR protected max.: | 35 kA |
with NZM1 125 A / 480 V AC |
Mechanical data | |
W x H x D: | 92 x 200 x 38 |
weight: | 81.0 kg/100 |
poles: | 3-pole |
for busbars: | 12, 15, 20, 25, 30 x 5, 10 and section busbars |
There must be a clearance of at least 10 mm above the article to remove it from the busbar system. | |
short-circuit withstandability: | the short-circuit capacity of the combination of adapter and MCCB depends on the MCCB |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com