Company
Innovations
Products
for UL feeder circuits >250V
The picture may show a similar product.
Part No.: 33217 000
NH fuse switch-disconnector size 000, 125 A, panel mounting
box terminal
for mounting plate
System
Panel
Advantages of the product
Self-closing inspection holes are available in the cover.
Product group | 09 |
Subgroup | 01 |
pack size | 1 |
EAN | 4021267332174 |
ECLASS 6.1 | 27142108 |
ECLASS 7.1 | 27142108 |
ETIM 4.0 | EC001040 |
ETIM 5.0 | EC001040 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
UL 4248-1
Approvals
IEC (CB) , UL , CCC , DNV GL
for UL feeder circuits >250V
type number: LTS-000
for fuse links size: | NH 000 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 9 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Details IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
rated current (IEC): | 125 A |
rated voltage (IEC) AC: | 690 V |
rated voltage (IEC) DC: | 440 V |
rated isolation voltage Ui AC: | 800 V |
rated isolation voltage Ui DC: | 500 V |
rated surge voltage Uimp : | 6 kV |
Utilisation category AC (IEC 60947-3) : | AC-21B (690 V / 80 A) AC-22B (400 V / 125 A) |
Utilisation category DC (IEC 60947-3) : | DC specifications: 2 current paths (L1,L3) in series DC-22B (440V/63A) DC-22B (220V/100A) DC-21B (440V/80A) DC-21B (220V/125A) |
cond. short-circuit current with fuses (AC): | 50 kA / 690 V |
approved wth fuse links of operation class: | gG |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 3,2 W.
(The power dissipation at full load would be 5,0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) DC: | 800 V |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
In accordance with the specified AC and DC switching properties and in consideration of the overload conditions, certain distances to earthed metal parts are to be adhered to. detailed information upon inquiry When several devices are used side-by-side in continuous operation, the rated load factor specified in IEC / EN 61439-1, Table 1, must be observed. |
Details UL | |
Standards | |
UL 4248-1 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 125 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR: | 100 kA |
Mechanical data | |
W x H x D: | 89 x 143 x 75 |
weight: | 57,2 kg/100 |
poles: | 3-pole |
Mounting: | for mounting plate |
front degree of protection: | IP30 |
Terminal points | |
cage clamp connection | |
screw drive: | S4 |
min. cross-section: | 1,5 mm² |
max. cross-section: | 50 mm² |
re: | 1.5 - 10 mm² |
rm: | 16 - 50 mm² |
f: | 2.5 - 50 mm² |
f + AE: | 1.5 - 50 mm² |
(f + AE may not fit with max. cross-section) | |
Not suitable for aluminium cables ! | |
Terminal space: | 10 x 10 |
Not suitable for aluminium cables ! | |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
permitted power dissipation of the fuse-link: | 9 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
for UL feeder circuits >250V |
33247
000
rapid mounting set
for 1 mouinting rail
size 000
More
33906
000
comb-type busbar, 3-pole, for 2 NH fuse switch disconnectors
35 mm²
for: 33217
More
33907
000
connecting terminal, front connection
for 3-pole comb-type busbar 35 mm², suitable for NH-fuse-switch-disconnector size 000 with box terminal
4 - 35 mm²
More
33219
000
trim frame, single
130 x 210
size 000
More
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com