busbar adapter 100 A, 3-pole (32981)

The picture may show a similar product.

Description

Part No.: 32981 000A

EQUES®60Classic

busbar adapter 100 A, 3-pole

for circuit breaker ABB MS49x and Siemens Sirius frame size S3, 200 mm long

72 x 200, with leads AWG 4 (25 mm²), with metal plate, top connection to the system

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

System

60Classic

Advantages of the product

Conductor ends ultrasonically sealed.
Click mechanism when pushing onto the busbar.

Product group 05
Subgroup 28
pack size 1
EAN 4021267329815
ETIM 5.0 EC001531
ETIM 8.0 EC001531

Approvals

Standards

IEC 61439-1:2020

UL 508

Approvals

CSA , UL

for UL feeder circuits >250V

type number: EEC60100-L

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2020
Electrical data IEC
rated current (IEC): 100 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 6 kV

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 4.6 W.

(The power dissipation at full load would be 7.3 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

min. permitted operation temperature -40°C
Details UL
Standards
UL 508
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 100 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR protected max.: 65 kA
SCCR: 65 kA with MS49x / 480 V AC
65 kA with S3 / 480 V AC
Mechanical data
W x H x D: 72 x 200 x 55
weight: 66.0 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
Material properties
halogen-free: Yes

Application notes

the short-circuit capacity of the combination of adapter and MCCB depends on the MCCB

for UL feeder circuits >250V