Company
Innovationen
Products
The picture may show a similar product.
Part No.: 31409000
CUSTO®60Classic
D-fuse base, busbar mounted, 57mm
for busbar 10 mm, gauge ring
E 33 / 3P
for busbars 12, 15, 20, 25, 30 x 10 and section busbars
System
60Classic
Product group | 01 |
Subgroup | 24 |
pack size | 10 |
EAN | 4021267314095 |
ECLASS 6.1 | 27142103 |
ECLASS 7.1 | 27142103 |
ETIM 4.0 | EC000094 |
ETIM 5.0 | EC000094 |
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-3:2010 + A1:2013 + A2:2019
Approvals
DNV GL
fuse links acc. to standard: | IEC / HD 60269-3 |
permitted power dissipation of the fuse-link: | 7 W |
Details IEC | |
Standards | |
IEC 60269-1:2006 + A1:2009 + A2:2014 IEC 60269-3:2010 + A1:2013 + A2:2019 |
Electrical data IEC | |
Rated current (IEC): | 63 A |
rated voltage (IEC) AC: | 500 V |
rated voltage (IEC) DC: | 500 V |
rated surge voltage Uimp : | 4 kV |
approved wth fuse links of operation class: | gG |
short-circuit strength when protected by fuses: | 50 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 6.4 W.
(The power dissipation at full load would be 10.0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 725 V |
max. permitted voltage (IEC) DC: | 630 V |
Contacting of the fuse links on the busbar via silvered copper plate | |
for fuse links and gauge rings as per DIN VDE 0636-3 IEC / HD 60269-3 | |
as per DIN VDE 0636 Part 3011, also 690V |
Mechanical data | |
W x H x D: | 57 x 200 x 43 |
weight: | 31.6 kg/100 |
poles: | 3-pole |
for busbars: | 12, 15, 20, 25, 30 x 10 and section busbars |
Type of fastening: Click mechanism protects against movement Contact pressure provided by screw cap Tightening torque of box terminals 3 Nm
Terminal points | |
Not suitable for aluminium cables ! |
There must be a clearance of at least 10 mm above the article to remove it from the busbar system. | |
Not suitable for aluminium cables ! | |
permitted power dissipation of the fuse-link: | 7 W |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com