Company
Innovations
Products
for UL feeder circuits >250V
The picture may show a similar product.
Part No.: 01319 000
CRITO®
brace terminal
lam. Cu. 20x3 ... 30x10
for busbars 20, 25, 30 x 5, 10 and section busbars
System
60Classic, centre feed unit, 100Energy
Advantages of the product
Terminal with captive clamping screws, conductor can be overlapped, indication of nominal cross-section and tightening torque noted on the terminal. Contact between conductor and busbar via contact block.
| Product group | 07 |
| Subgroup | 20 |
| pack size | 6 |
| EAN | 4021267013196 |
| ECLASS 6.1 | 27141146 |
| ECLASS 7.1 | 27141146 |
| ETIM 4.0 | EC000001 |
| ETIM 5.0 | EC000001 |
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Approvals
UL
type number: 519
UL file: E123577, UL category (for USA): NMTR2 https://www.ul.com
CCC approval: no certification required
| Details IEC | |
| Standards | |
|
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
| Electrical data IEC | |
| rated current (IEC): | 500 A |
| rated voltage (IEC) AC: | 690 V |
| Supplementary data IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
| max. permitted voltage (IEC) AC: | 1000 V |
| max. permitted voltage (IEC) DC: | 1500 V |
| current carrying capacity for centre feed: | 750 A |
| current capacity (IEC) max.: | 750 A |
| Details UL | |
| Standards | |
| UL 508 |
| Electrical data UL | |
| rated current (UL): | 800 A |
| rated voltage (UL) AC: | 600 V |
| rated frequency (UL): | 50 / 60 Hz |
| SCCR: | 25 kA |
| Mechanical data | |
| W x H x D: | 38 x 51 x 70 |
| weight: | 30.3 kg/100 |
| for busbars: | 20, 25, 30 x 5, 10 and section busbars |
| Terminal points | |
| screw clamp connection | |
| screw drive: | S8 |
| min. cross-section: | 60 mm² |
| max. cross-section: | 240 mm² |
| Md min.: | 24.0 Nm |
| Md max.: | 36.0 Nm |
| Not suitable for aluminium cables ! | |
| Terminal space: | 30 x 20 |
| lam. Cu width: | 20 - 24 mm |
| lam. Cu thickness: | 3 - 10 mm |
| number of lam. Cu: | 1 |
| Not suitable for aluminium cables ! | |
| The insulation performance of the article depends on the installation conditions. | |
|
CSA certificate on request |
|