Company
Innovations
Products
The picture may show a similar product.
Part No.: 01480000A
longitudinal busbar connector
40 mm
for busbars 30, 40, 80, 100 x 10
System
185Power
Product group | 07 |
Subgroup | 33 |
pack size | 3 |
EAN | 4021267014803 |
ECLASS 6.1 | 27400606 |
ECLASS 7.1 | 27400606 |
ETIM 4.0 | EC000713 |
ETIM 5.0 | EC000713 |
Standards
IEC 61439-1:2020
UL 508
Approvals
UL
for UL feeder circuits >250V
type number: CR185-C40
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
rated voltage (IEC) AC: | 690 V |
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 1000 V |
max. permitted voltage (IEC) DC: | 1500 V |
current capacity (IEC) max.: | 750 A |
the busbar connector was tested in an arrangment where the busbar supports at the connection of the 2 systems had a spacing of 200 mm test conditions: 100x10 - 100x10 (1x 01480 + 1x 01481) peak withstand current Ipk: 106 kA Icw (1,0 s): 50 kA test conditions: 80x10 - 80x10 (2x 01480) peak withstand current Ipk: 106 kA Icw (1,0 s): 50 kA test conditions: 40x10 - 40x10 (1x 01480) peak withstand current Ipk: 81 kA Icw (1,0 s): 34 kA test conditions: 30x10 - 30x10 (1x 01480) peak withstand current Ipk: 81 kA Icw (1,0 s): 34 kA |
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 700 A |
rated voltage (UL) AC: | 1000 V |
rated frequency (UL): | 50 / 60 Hz |
rated voltage (UL) DC: | 1000 V |
SCCR unprotected max.: | 42 kA |
3 cycles (without OPD) @ 1000 V AC |
Mechanical data | |
W x H x D: | 47 x 40 x 49 |
weight: | 48,0 kg/100 |
for busbars: | 30, 40, 80, 100 x 10 |
permitted busbar displacement: | 1 |
permitted spacing between systems: | 11 - 14 mm |
Terminal points | |
screw clamp connection | |
M10 | |
screw drive: | SW17 |
Md min.: | 35,0 Nm |
Md max.: | 40,0 Nm |
The insulation performance of the article depends on the installation conditions. | |
Reference |
one terminal is required to connect busbars 30x10 |
for UL feeder circuits >250V |