Part No.: 32752000A
EQUES®185Power
busbar adapter 1550 A
300 x 675, connection top, clamp connection
for Socomec Sirco 1250 A (Socomec-Nr. 26003U21), Sirco 1600 A (Socomec-Nr. 26003U61)
for busbars 30, 40, 60, 80, 100, 120 x 10
System
185Power
Product group | 05 |
Subgroup | 48 |
pack size | 1 |
EAN | 4021267327521 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Standards
IEC 61439-1:2020
UL 508
Approvals
UL
for UL feeder circuits >250V
type number: EQ185-A1600-C
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
Rated current (IEC): | 1550 A |
rated voltage (IEC) AC: | 690 V |
rated voltage (IEC) DC: | 800 V |
rated isolation voltage Ui AC: | 1000 V |
rated isolation voltage Ui DC: | 1000 V |
rated surge voltage Uimp : | 12 kV |
rated peak withstand current Ipk max.: | 106 kA |
rated short-time withstand current Icw (1.0 s) max.: | 50 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 406,4 W.
(The power dissipation at full load would be 635,0 W.)
with Socomec Sirco 1250 A (Socomec no.26003U21) and 1600 A (Socomec no.26003U61) usable up to 1550 A maximum 300 switching cycles |
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 1200 A |
rated voltage (UL) AC: | 1000 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 50 kA |
3 cycles (without OPD) @ 1000 V AC |
Mechanical data | |
W x H x D: | 300 x 652 x 76 |
weight: | 3350,0 kg/100 |
poles: | 3-pole |
for busbars: | 30, 40, 60, 80, 100, 120 x 10 |
CT can be integrated in the device: | ja |
short-circuit withstandability: | Die Kurzschlusswerte der Kombination aus Sammelschienenadapter und Lasttrennschalter hängen von den zulässigen Einbaubedingungen des Schaltgerätes ab. Diese Werte sind bei Wöhner zu erfragen. |
for UL feeder circuits >250V |