Company
Innovations
Products
The picture may show a similar product.
Part No.: 31300000
AMBUS®Panel
holder for cylindrical fuses, with LED
Class CC / 3P
30 A / 600 V
indication of a released fuse link
for mounting rail
System
Panel
Advantages of the product
large clamping range, also for two identical conductors (adjacent)
holder for label
with indicator for tripped fuse
any polarity for DC voltage
Product group | 17 |
Subgroup | 07 |
pack size | 4 |
EAN | 4021267313005 |
ECLASS 6.1 | 27142190 |
ECLASS 7.1 | 27142190 |
ETIM 4.0 | EC002705 |
ETIM 5.0 | EC002705 |
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system J
UL 4248-1
UL 4248-4
Approvals
CSA , UL , CCC
for UL feeder circuits >250V
type number: AESCC
UL file: E230163, UL category (for USA): IZLT https://www.ul.com
UL file: E230163, UL category (for Canada): IZLT7 https://www.ul.com
CSA file: 110285, CSA class: 6225-01 https://directories.csa-international.org
CCC certificate: 21107299296
for fuse links size: | Class CC |
fuse links acc. to standard: | UL 248-4 |
permitted power dissipation of the fuse-link: | 4 W |
Details IEC | |
Standards | |
IEC 60269-1:2006 + A1:2009 + A2:2014 IEC 60269-2:2013 + A1:2016, Fuse system J |
Electrical data IEC | |
min. operating voltage AC: | 110 V |
min. operating voltage DC: | 110 V |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 0,6 W.
(The power dissipation at full load would be 0,9 W.)
indicator light operating voltage range: 110 - 600 V AC / DC |
Details UL | |
Standards | |
UL 4248-1
UL 4248-4 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Electrical data UL | |
rated current (UL): | 30 A |
rated voltage (UL) AC: | 600 V |
min. operating voltage AC: | 110 V |
rated frequency (UL): | 50 / 60 Hz |
rated voltage (UL) DC: | 600 V |
min. operating voltage DC: | 110 V |
SCCR: | 200 kA |
Mechanical data | |
W x H x D: | 54 x 81 x 58 |
weight: | 18,5 kg/100 |
poles: | 3-pole |
Mounting: | for mounting rail |
degree of protection: | IP20 |
front degree of protection: | IP20 |
Terminal points | |
cage clamp connection | |
screw drive: | PZ2 |
wire stripping: | 11 mm |
min. cross-section: | 0,75 mm² |
max. cross-section: | 25 mm² |
Md min.: | 2,0 Nm |
Md max.: | 2,5 Nm |
Not suitable for aluminium cables ! | |
min. cross-section UL: | AWG 18 |
max. cross-section UL: | AWG 4 |
for applications acc. to IEC / EN : |
Not suitable for aluminium cables ! | |
Reference |
The indicator light signals that the fuse has tripped, but only when the closed fuse-holder is under voltage. |
permitted power dissipation of the fuse-link: | 4 W |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com