switch disconnector with fuses, 3-pole (33511)

The picture may show a similar product.

Description

Part No.: 33511000

QUADRON®60Classic Speed

switch disconnector with fuses, 3-pole

screw M10, connection top

size 1

double-breaking

operator independent switching (snap-action mechanism)

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

System

60Classic

Advantages of the product

With spring-controlled switch mechanism for frequent switching as per utilisation category "A"
Can be locked in neutral position with up to 3 padlocks
FLAG indicator shows the switch setting
Fuses can be changed safely and without tools thanks to double-breaking main contacts
Additional visible separating section by removing the cover incl. fuses
Can be used as mains disconnector as per IEC / EN 60204-1 (main switch).

CrossLink® adapter technology
Simple and safe clicking into place and making contact
Busbar supports can be mounted above each other for flat rails

Product group 15
Subgroup 23
pack size 1
EAN 4021267335113
ECLASS 6.1 27371401
ECLASS 7.1 27371401
ETIM 4.0 EC001040
ETIM 5.0 EC001040

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

Approvals

IEC (CB) , VDE , DNV GL

type number: QCS-NH1

Technical data

for fuse links size: NH 1
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 23 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
rated current (IEC): 250 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 8 kV
Utilisation category AC (IEC 60947-3) : AC-23B (690V/250A)
AC-23A (500V/250A)
AC-22A (690V/250A)
cond. short-circuit current with fuses (AC): 50 kA / 690V
approved wth fuse links of operation class: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 56,3 W.

(The power dissipation at full load would be 88,0 W.)

Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals.
When several devices are used side-by-side in continuous operation, the rated load factor specified in VDE 0660 Part 500 / EN 60 439-1, Table 1, must be observed.
System component: degree of protection IP20 at front as per DIN EN 60529, degree of protection near terminal depends on installation; shock protection as per DIN EN 50274

adapter module: front side degree of protection IP20 as per DIN EN 60529 (finger-safe)
Mechanical data
W x H x D: 184 x 314 x 194
weight: 589,0 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars

Busbar connector: externally tensioned contacting, convenient click mechanism, simple conversion of the combination bases from 5 to 10mm-thick busbars.

When installing QCS, a busbar support is to be applied left and right, see assembly manual.

Terminal points
screw connection
M10
screw drive: SW16
Md min.: 30,0 Nm
Md max.: 35,0 Nm

Application notes

permitted power dissipation of the fuse-link: 23 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.

Links

Downloads

Accessories

33142000
cover for cable lugs, top / bottom attachable
for: QCB-NH1, QCS-NH1, QCS-320
More

33145000
prism terminal, double, for Cu cables
2x 35 - 70 mm²
for: QCB-NH1, QCS-NH1, QCS-320
More

33163000
clamp connector for Cu cables
70 - 150 mm²
for: QCB-NH1, QCS-NH1, LTS-F 250, LTS 400
More

33166000
prism terminal, single, for Cu cables
35 - 150 mm²
QCB-NH1, QCS-NH1, QCS-320
for: QCB-NH1, QCS-NH1, QCS-320
More

33908000
pilot switch for monitoring the switch position
changeover 250 V AC / 5 A, 30 V DC / 4 A
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320
More

33909000
box terminal for Cu cables
35 - 150 mm²
QCB-NH1, QCS-NH1, QCS-320
for: QCB-NH1, QCS-NH1, QCS-320
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com