The picture may show a similar product.
Part No.: 33202 000
QUADRON®Panel
NH fuse switch-discon. size 2, 400 A, panel mounting
screw M10
for mounting plate
System
Panel
Advantages of the product
Disconnectors are equipped with arc chambers.
The shock protection is split into 2 for safe connection of the conductors.
Self-closing inspection holes are available in the cover.
| Product group | 09 |
| Subgroup | 09 |
| pack size | 1 |
| EAN | 4021267332020 |
| ECLASS 6.1 | 27142108 |
| ECLASS 7.1 | 27142108 |
| ETIM 4.0 | EC001040 |
| ETIM 5.0 | EC001040 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
UL 4248-1
Approvals
IEC (CB) , UL , CCC , DNV GL
for UL feeder circuits >250V
type number: LTS-2
| for fuse links size: | NH 2 |
| fuse links acc. to standard: | IEC / HD 60269-2 |
| permitted power dissipation of the fuse-link: | 34 W |
| requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
| Details IEC | |
| Standards | |
|
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
| Electrical data IEC | |
| rated current (IEC): | 400 A |
| rated voltage (IEC) AC: | 690 V |
| rated voltage (IEC) DC: | 440 V |
| rated isolation voltage Ui AC: | 800 V |
| rated isolation voltage Ui DC: | 500 V |
| rated surge voltage Uimp : | 6 kV |
| Utilisation category AC (IEC 60947-3) : | AC-23B (400V) AC-22B (690V) AC-21B (690V) AC-20B (1000V) at pollution degree 2 visible information required if used at more than 690V AC: do not switch under load |
| Utilisation category DC (IEC 60947-3) : | DC specifications: 2 current paths (L1,L3) in series DC-22B (440V) DC-21B (440V) DC-20B (1000V) at pollution degree 2 visible information required if used at more than 440V DC: do not switch under load |
| cond. short-circuit current with fuses (AC): | 50 kA / 690 V |
| approved wth fuse links of operation class: | gG |
| rated peak withstand current Ipk max.: | 27.2 kA |
| rated short-time withstand current Icw (1.0 s) max.: | 13.2 kA |
| Icw approved with: | Trennmesser |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 14,1 W.
(The power dissipation at full load would be 22,0 W.)
| Supplementary data IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
| max. permitted voltage (IEC) DC: | 800 V |
| A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
| Entsprechend den angegeben AC- und DC- Schalteigenschaften und unter Berücksichtigung der Überlastbedingungen, sind gewisse Abstände zu geerdeten Metallteilen einzuhalten. Nähere Informationen auf Anfrage. Bei Verwendung als Trennschalter ist die Einhaltung der Abstände nicht erforderlich. |
|
| Degree of protection IP30 at front, degree of protection near terminal depends on installation |
| Details UL | |
| Standards | |
| UL 4248-1 |
| for UL feeder circuits >250V |
| Electrical data UL | |
| rated current (UL): | 400 A |
| rated voltage (UL) AC: | 600 V |
| rated frequency (UL): | 50 / 60 Hz |
| SCCR: | 100 kA |
| Mechanical data | |
| W x H x D: | 210 x 288 x 128 |
| weight: | 362,0 kg/100 |
| poles: | 3-pole |
| Mounting: | for mounting plate |
| front degree of protection: | IP30 |
| Terminal points | |
| screw connection | |
| M10 | |
| screw drive: | SW16 |
| Md min.: | 30,0 Nm |
| Md max.: | 35,0 Nm |
|
based on the AC and DC switching capacities and considering the overload conditions as given in the above mentioned standards the following distances to earthed metal parts have to be respected: |
|
| required spacing top: | 30 mm |
| required spacing at sides: | 20 mm |
| A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
| permitted power dissipation of the fuse-link: | 34 W |
| requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
| for UL feeder circuits >250V | |
33158
000
rapid mounting set
for 2 mounting rails, rails centre distance 125 mm or 150 mm
size 1 - 2
More
33146
000
prism terminal, double, for Cu cables
2x 70 - 120 mm²
size 2
More
33164
000
clamp connector for Cu cables
120 - 240 mm²
for: QCB-NH2, LTS-F 400, LTS 630
More
33167
000
prism terminal, single, for Cu cables
50 - 240 mm²
More
33271
000
extension for 2 cable lugs
size 1 - 2
More
33143
000
cover for cable lugs, top / bottom attachable
for QCB-NH2
for: QCB-NH2
More
33153
000
trim frame, single
248 x 330
size 2
More
33155
000
barrier for handle
for NH fuse-switch disconnector size 1-3
for closing of handle area from rear
More
33418
000
connection shroud
for NH fuse-switch-disconnector size 2
More
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de