busbar adapter 570 A, 3-pole (32157)

The picture may show a similar product.

Description

Part No.: 32157 000

EQUES®60Classic

busbar adapter 570 A, 3-pole

140 x 270

connection to the system top or bottom

for Schneider Electric NS400, NS630, NSX400, NSX630

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

System

60Classic

Product group 05
Subgroup 42
pack size 1
EAN 4021267321574
ETIM 5.0 EC001531
ETIM 8.0 EC001531

Approvals

Standards

IEC 61439-1:2020

UL 508

Approvals

CSA , UL , DNV GL

for UL feeder circuits >250V

type number: 60630.1-L

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2020
Electrical data IEC
rated current (IEC): 570 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 6 kV

NS 630: 35 kA @ 600 V / Id = 37 kA
NS 630: 100 kA @ 400 V / Id = 46 kA

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 25,7 W.

(The power dissipation at full load would be 40,2 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

min. permitted operation temperature -40
Details UL
Standards
UL 508
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 600 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR protected max.: 65 kA
SCCR: 25 kA with NS630 / 600 V AC
50 kA with NS630 / 480 V AC
50 kA with NSX630 / 600 V AC, max. busbar support distance 400 mm
65 kA with NS400 / 480 V AC
65 kA with NSX630 / 480 V AC, max. busbar support distance 400 mm
35 kA with NS400 / 600 V AC
Mechanical data
W x H x D: 140 x 272 x 35
weight: 222,6 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
Material properties
halogen-free: Yes

Application notes

There must be a clearance of at least 10 mm above the article to remove it from the busbar system.

the short-circuit capacity of the combination of adapter and MCCB depends on the MCCB

for UL feeder circuits >250V

Links

Downloads

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com