            Company
            
        
        
            Innovations
            
        
        
      
        
            Products
            
        
      	
        
        
        
    The picture may show a similar product.
Part No.: 32584 000
EQUES®60Classic
busbar adapter 250 A, 4-pole
140 x 270
N on left side
connection to the system top
for ABB Tmax T4
for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars
System
60Classic
| Product group | 05 | 
| Subgroup | 36 | 
| pack size | 1 | 
| EAN | 4021267325848 | 
| ECLASS 6.1 | 27370304 | 
| ECLASS 7.1 | 27370304 | 
| ETIM 4.0 | EC001531 | 
| ETIM 5.0 | EC001531 | 
Standards
IEC 61439-1:2020
UL 508
Approvals
CSA , UL
																		 
																		 
for UL feeder circuits >250V
type number: EPC60250-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
CCC approval: no certification required
| Details IEC | |
| Standards | |
| IEC 61439-1:2020 | 
| Electrical data IEC | |
| rated current (IEC): | 250 A | 
| rated voltage (IEC) AC: | 690 V | 
| rated isolation voltage Ui AC: | 800 V | 
| rated surge voltage Uimp : | 6 kV | 
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 8,1 W.
(The power dissipation at full load would be 12,6 W.)
| Details UL | |
| Standards | |
| UL 508 | 
| for UL feeder circuits >250V | 
| Electrical data UL | |
| rated current (UL): | 250 A | 
| rated voltage (UL) AC: | 600 V | 
| rated frequency (UL): | 50 / 60 Hz | 
| SCCR unprotected max.: | 22 kA | 
| 3 cycles (without OPD) @ 600 V AC | |
| SCCR protected max.: | 200 kA | 
| SCCR: | 200 kA with 3VA61 150 A, 3VA62 250 A / 240 V AC 50 kA with 3VA61 150 A, 3VA62 250 A / 600 V AC 150 kA with 3VA61 150 A, 3VA62 250 A / 480 V AC | 
| Mechanical data | |
| W x H x D: | 140 x 270 x 35 | 
| weight: | 180,0 kg/100 | 
| poles: | 3-pole+N | 
| for busbars: | 12, 15, 20, 25, 30 x 5, 10 and section busbars | 
| There must be a clearance of at least 10 mm above the article to remove it from the busbar system. | |
| the short-circuit capacity of the combination of adapter and MCCB depends on the MCCB | |
| for UL feeder circuits >250V | 
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com