Company
Innovationen
Products
The picture may show a similar product.
Part No.: 31963000
AMBUS®60Classic
busbar mounted fuse holder
for fuses 10x38 IEC 60269-2
10 x 38 / 4P
for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars
System
60Classic
Product group | 01 |
Subgroup | 46 |
pack size | 4 |
EAN | 4021267319632 |
ECLASS 6.1 | 27142190 |
ECLASS 7.1 | 27142190 |
ETIM 4.0 | EC002705 |
ETIM 5.0 | EC002705 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
IEC (CB) , VDE , CCC
type number: AEL10x38
CCC certificate: 21107317604
for fuse links size: | 10x38 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 3 W |
Details IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
rated current (IEC): | 32 A |
rated voltage (IEC) AC: | 690 V |
rated voltage (IEC) DC: | 440 V |
rated surge voltage Uimp : | 6 kV |
Utilisation category AC (IEC 60947-3) : | AC 20B (690 V) |
approved wth fuse links of operation class: | gG |
short-circuit strength when protected by fuses: | 100 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 0,6 W.
(The power dissipation at full load would be 1,0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 725 V |
max. permitted voltage (IEC) DC: | 462 V |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
for fuse links as per IEC / EN 60269-2 (gG, max. 3W) |
Mechanical data | |
W x H x D: | 27 x 260 x 63 |
weight: | 25,2 kg/100 |
poles: | 3-pole+N |
for busbars: | 12, 15, 20, 25, 30 x 5, 10 and section busbars |
Type of fastening: patented click mechanism
Terminal points | |
Not suitable for aluminium cables ! | |
nach IEC: Cu 1.5 … 6 mm2 (f, re) |
Not suitable for aluminium cables ! | |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
permitted power dissipation of the fuse-link: | 3 W |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com