The picture may show a similar product.
订货号 31232 000
SECUR®60Classic PowerLiner
隔离开关熔断器组,母线式
适用熔断体 10x38 IEC 60269-2
63 A / 3 极
下端接电缆
适用母线 12, 15, 20, 25, 30 x 5, 10 和异型母线
3-pole / 1-pole switching
系统
60Classic
| 产品组 | 01 | 
分组  | 
																	42 | 
| 包装件数 | 1 | 
| EAN | 4021267312329 | 
| ECLASS 6.1 | 27142190 | 
| ECLASS 7.1 | 27142190 | 
| ETIM 4.0 | EC002705 | 
| ETIM 5.0 | EC002705 | 
标准
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
型号: SPL-10x38
| for fuse links size: | 10x38 | 
| fuse links acc. to standard: | IEC / HD 60269-2 | 
| 所使用熔断器的允许损耗功率: | 3 W | 
| Details IEC | |
| 标准 | |
| 
																		IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only  | 
																
| Electrical data IEC | |
| 端部供电(IEC): | 32 A | 
| 额定电压(IEC)AC: | 690 V | 
| 额定电压 (IEC) DC: | 110 V | 
| rated isolation voltage Ui AC: | 500 V | 
| 额定绝缘电压 Ui DC: | 250 V | 
| 额定冲击耐受电压 Uimp: | 6 kV | 
| 使用等级 AC (IEC 60947-3): | AC-23A (400 V)  | 
															
| 带熔断器时的条件额定短路电流: | 50 kA / 400 V (32A) | 
| 带熔断器测定的工作等级: | gG | 
功率输出:
The power dissipation at a typical load of 80 % results to 3.4 W.
(The power dissipation at full load would be 5.3 W.)
| Supplementary data IEC | |
| 
																	 下述参数已经在特定条件下通过测试得到验证。开始设计之前,请联系维纳尔咨询这些条件。  | 
															
| 最大电压 IEC AC: | 725 V | 
| 符合 IEC 60947-3 的熔断器组合电器,只有在作为没有分断能力的熔断器式隔离器时、在不超过额定绝缘电压使用并进行相应的标识时,才允许超过额定工作电压运行。 | 
| 适用于 gG和aM熔断器, 符合IEC / EN 60269-2标准 | |
The function of isolation between incoming and outgoing contacts is provided by the opening of the switching mechanism as required in the standard.  | 
															
| 机械数值 | |
| 宽 x 高 x 厚: | 27 x 220 x 100 | 
| 重量: | 76.0 kg/100 | 
| 极数: | 3 极 | 
| 适用母线: | 12, 15, 20, 25, 30 x 5, 10 和异型母线 | 
| 正面防护等级: | IP20 | 
Type of fastening: patented click mechanism
| 连接端 | |
| cage clamp connection | |
| screw drive: | PZ2 | 
| wire stripping: | 12 mm | 
| min. cross-section: | 1.5 mm² | 
| 最大横截面积: | 16 mm² | 
| Md min.: | 2.0 Nm | 
| Md max.: | 2.5 Nm | 
| Not suitable for aluminium cables ! | |
| Not suitable for aluminium cables ! | |
| 符合 IEC 60947-3 的熔断器组合电器,只有在作为没有分断能力的熔断器式隔离器时、在不超过额定绝缘电压使用并进行相应的标识时,才允许超过额定工作电压运行。 | |
| 所使用熔断器的允许损耗功率: | 3 W | 