Innovationen
Prodotti
The picture may show a similar product.
Cod.art.: 33851000A
CAPUS®Panel
Sezionatore sottocarico, 3poli + N
morsetti a gabbia 2,5 - 16 mm² / WG 16 - 6, manovra giallo -rosso
40 A
N sul lato sinistro
for mounting plate or mounting rail
Montaggio
Panel
Vantaggi prodotto
lockable in 0-position with a padlock (max. 4 mm diameter)
gruppo di prodotto | 14 |
sottogruppo prodotto | 01 |
pz/ conf. | 1 |
EAN | 4021267338510 |
ECLASS 6.1 | 27371403 |
ECLASS 7.1 | 27371403 |
ETIM 4.0 | EC000216 |
ETIM 5.0 | EC000216 |
Norme
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
UL 60947-4-1
Omologazioni
UL
type no.: SD1-4-40-R
UL file: E506215, UL category (for USA): NLRV https://www.ul.com
UL file: E506215, UL category (for Canada): NLRV7 https://www.ul.com
Details IEC | |
Norme | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
corrente nominale (IEC): | 40 A |
tensione nominale (IEC) AC: | 690 V |
frequenza nominale (IEC): | 50 / 60 Hz |
tensione nominale di isolamento Ui AC: | 800 V |
tensione di picco Uimp: | 4 kV |
Categoria d'impiego AC: | AC-23 A (690 V / 40 A) AC-22 A (690 V / 40 A) AC-21 A (690 V / 40 A) |
corrente nom. di cto cto condizionata da fusibili (AC): | 10 kA |
secondo prove fatte con fusibili di caratteristica: | gG |
corrente nom. di breve durata Icw (1,0 s) max.: | 1 kA |
potere nominale di chiusura: | 2,1 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 0,8 W.
(The power dissipation at full load would be 1,2 W.)
Details UL | |
Norme | |
UL 60947-4-1 |
Electrical data UL | |
corrente nominale (UL): | 40 A |
tensione nominale (UL) AC: | 600 V |
frequenza nominale (UL): | 50 / 60 Hz |
for wires UL: | Cu 75°C |
SCCR protected max.: | 5 kA |
5 kA with fuse max. 40 A / 600 V AC |
Valori meccanici | |
L x A x P: | 51 x 81 x 79 |
peso: | 20,5 kg/100 |
Poli: | 3 poli + N |
Mounting: | for mounting plate or mounting rail |
grado di protezione: | IP20 |
Connessioni | |
cage clamp connection | |
wire stripping: | 10 mm |
min. cross-section: | 2,5 mm² |
max. cross-section: | 16 mm² |
re: | 2.5 - 16 mm² |
rm: | 16 - 16 mm² |
f: | 2.5 - 16 mm² |
f + AE: | 2.5 - 16 mm² |
(f + AE may not fit with max. cross-section) | |
Md min.: | 2,0 Nm |
Md max.: | 2,0 Nm |
Not suitable for aluminium cables ! | |
min. cross-section UL: | AWG 16 |
max. cross-section UL: | AWG 6 |
torque (UL): | 17,7 lb-in |
for wires UL: | Cu 75°C |
Not suitable for aluminium cables ! | |
Avvisi e consigli |
N-pole :
Two connection space covers are necessary for each the top and the bottom of a 3P+N switch: 3-pole and 1-pole. |
Trova il tuo contatto
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com