Cod.art.: 32454000
EQUES®60Classic
Adattatore EEC 63 A
con 1 guida DIN scorrevole
54 x 200, con cavi AWG 8 (10 mm²)
per barre 12, 15, 20, 25, 30 x 5, 10 e barre profilate
Montaggio
60Classic
Vantaggi prodotto
Conductor ends ultrasonically sealed.
Click mechanism when pushing onto the busbar.
gruppo di prodotto | 05 |
sottogruppo prodotto | 24 |
pz/ conf. | 4 |
EAN | 4021267324544 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Norme
IEC 61439-1:2020
UL 508
Omologazioni
CSA , UL , DNV GL
for UL feeder circuits >250V
type no.: EEC6063-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
Omologazione CCC : no certification required
Details IEC | |
Norme | |
IEC 61439-1:2020 |
Electrical data IEC | |
corrente nominale (IEC): | 63 A |
tensione nominale (IEC) AC: | 690 V |
tensione nominale di isolamento Ui AC: | 800 V |
tensione di picco Uimp: | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 4,4 W.
(The power dissipation at full load would be 6,9 W.)
Details UL | |
Norme | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
corrente nominale (UL): | 65 A |
tensione nominale (UL) AC: | 600 V |
frequenza nominale (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 7,5 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
SCCR: |
100 kA with JDDZ fuse Class CC, CF, J or T 60 A / 600 V AC
65 kA with any NKJH/7 Comb. Motor Controller Type E 65 A / 480 V AC 65 kA with any DIVQ/7 circuit breaker 60 A / 480 V AC |
Valori meccanici | |
L x A x P: | 54 x 200 x 63 |
peso: | 39,2 kg/100 |
Poli: | 3 poli |
per barre: | 12, 15, 20, 25, 30 x 5, 10 e barre profilate |
There must be a clearance of at least 12 mm above the article to remove it from the busbar system. | |
Avvisi e consigli |
For compact mounting of complete motor circuits with commercially available switchgear and safe mechanical and electrical connection to the busbar system. |
short-circuit withstandability: | the short-circuit capacity of the combination of adapter and motor starter depends on the motor starter |
for UL feeder circuits >250V |