Sezionatore sottocarico, 3 poli (33356)

The picture may show a similar product.

Descrizione

Cod.art.: 33356000

CAPUS®Panel

Sezionatore sottocarico, 3 poli

viti M10, manovra rossa

400 A

for mounting plate

Montaggio

Panel

Vantaggi prodotto

double-breaking main contacts, visible separation sections, user-independent switching, assembly and connection material contained in scope of delivery

gruppo di prodotto 14
sottogruppo prodotto 06
pz/ conf. 1
EAN 4021267333560
ECLASS 6.1 27371403
ECLASS 7.1 27371403
ETIM 4.0 EC000216
ETIM 5.0 EC000216

Certificazioni

Norme

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

Omologazioni

IEC (CB)

type no.: LTS-400

Dati tecnici

Details IEC
Norme
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
corrente nominale (IEC): 400 A
tensione nominale (IEC) AC: 500 V
tensione nominale di isolamento Ui AC: 1000 V
tensione di picco Uimp: 12 kV
Categoria d'impiego AC: AC-23B (500V)
AC-22B (500V)
AC-21B (500V)
secondo prove fatte con fusibili di caratteristica: gG
corrente nom. di breve durata Icw (1,0 s) max.: 15 kA
potere nominale di chiusura: 30 kA

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 36,5 W.

(The power dissipation at full load would be 57,0 W.)

Mechanical lifespan (switching operations) 7000
rated short-circuit making capacity 30kA
conv. therm. current in housing
400A, horizontal installation (adjacent poles) encapsulated 504 x 378 x 302mm
400A, vertical installation (poles beneath each other) encapsulated 500 x 500 x 300mm
Shock protection at front with terminal space cover IP40
Valori meccanici
L x A x P: 270 x 237 x 197
peso: 546,0 kg/100
Poli: 3 poli
Mounting: for mounting plate

Type of fastening: screw-on

connection screw (clamps and wedge clamp terminal can be retrofitted),
screw connection
M10, 28Nm ± 10% torque,
clamp connection for lam. Cu
terminal space 18x1-10mm,
6-8Nm torque
wedge clamp connection, single
cross-section 70 - 150mm², s(r), f, f+AE**  Cu - Al*,  6-8Nm torque
wedge clamp connection, double
cross-section 2 x 70 - 120mm², s(r), f, f+AE**  Cu,  6-8Nm torque

* Aluminium conductors must be prepared before connection in accordance with the pertinent technical recommendations. The connections are to be checked at regular intervals and serviced not later than every 6 months.
** reduction in the max. conductor cross-sections may be required.

Connessioni
Not suitable for aluminium cables !
  

viti M10 :
C. serr. 25 - 31 Nm

Application notes

Not suitable for aluminium cables !

Avvisi e consigli

When installing a cover, the switch-disconnector on the housing must not be closed, the safety instructions for the Emergency Stop switch must be observed.

Links

Downloads

Accessori

33163000
connessione a brida per cavi Cu
70 - 150 mm²
per: QCB-NH1, QCS-NH1, LTS-F 250, LTS 400
Di Più

33347000
microswitch di segnalazione posizione maniglia
1 NC + 1 NA, connettori piatti 6,3 x 0,8
LTS, LTS-F
Di Più

33348000
mecc. manovra rinviata
giallo-rosso, senza maniglia
con mecc. bloccoporta, lucchettabile
per: LTS-250/400/630, LTS-F 160/250/400
Di Più

33351000
Calotta di protezione terminali
per la copertura di tutti terminali, grigia
LTS-400/630, LTS-F 250/400
Di Più

33366000
morsetto a prisma per cavi Cu e Al
70 - 150 mm²
per: LTS-F 250, LTS 400
Di Più

33380000
asta lungh. 550mm
LTS-250/400/630, LTS-F 160/250/400
per: LTS-250/400/630, LTS-F 160/250/400
Di Più

23923000AD
asta lungh. 300 mm
per: S32 250 A / 400 A
NUOVO
Di Più

Similar products

33334000
CAPUS®Panel
Sezionatore sottocarico, 3 poli
viti M10, manovra nera
400 A
Di Più

Trova il tuo contatto

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com