Cod.art.: 01318 000
CRITO®
Morsetto a pinza
Cu / Al 95 - 185 mm²
per barre 20, 25, 30 x 5, 10 e barre profilate
Montaggio
60Classic, centre feed unit, 100Energy
Vantaggi prodotto
Terminal with captive clamp screws, conductor can be overlapped, indication of nominal cross-section and tightening torque noted on the terminal, contact between conductor and busbar via cable bed.
| gruppo di prodotto | 07 | 
| sottogruppo prodotto | 20 | 
| pz/ conf. | 6 | 
| EAN | 4021267013189 | 
| ECLASS 6.1 | 27141146 | 
| ECLASS 7.1 | 27141146 | 
| ETIM 4.0 | EC000001 | 
| ETIM 5.0 | EC000001 | 
Norme
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Omologazioni
UL
																		 
type no.: 518
UL file: E123577, UL category (for USA): NMTR2 https://www.ul.com
Omologazione CCC : no certification required
| Details IEC | |
| Norme | |
| IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 | 
| Electrical data IEC | |
| corrente nominale (IEC): | 300 A | 
| tensione nominale (IEC) AC: | 690 V | 
| resistenza nom. alla corrente di picco Ipk max.: | 55.8 kA | 
| Supplementary data IEC | |
| I seguenti valori sono stati rilevati tramite prove con determinate condizioni. Prima di progettare vostro impianto chiedere a Wöhner suddette condizioni. | 
| tensione max. ammissibile (IEC) AC: | 1000 V | 
| tensione max. ammissibile (IEC) DC: | 1500 V | 
| corrente d'impiego max. (IEC): | 500 A | 
| Details UL | |
| Norme | |
| UL 508 | 
| suitable for field-installed conductors | 
| Electrical data UL | |
| corrente nominale (UL): | 310 A | 
| tensione nominale (UL) AC: | 600 V | 
| frequenza nominale (UL): | 50 / 60 Hz | 
| SCCR: | 25 kA | 
| Valori meccanici | |
| L x A x P: | 38 x 51 x 70 | 
| peso: | 31.2 kg/100 | 
| per barre: | 20, 25, 30 x 5, 10 e barre profilate | 
| Connessioni | |
| min. cross-section: | 95 mm² | 
| max. cross-section: | 185 mm² | 
| Md min.: | 24.0 Nm | 
| Md max.: | 36.0 Nm | 
| Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. | |
| for applications acc. to IEC / EN : | |
| Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. | |
| La capacità di isolamento dell'articolo dipende dalle condizioni di installazione. | |
| CSA certificate on request | |