Selezione prodotto

for UL feeder circuits >250V

modulo di connessione (01594)

The picture may show a similar product.

Descrizione

Cod.art.: 01594000A

CRITO®CrossBoard

modulo di connessione

150 mm², per alimentazione posteriore del CrossBoard

3p

connessione cavi in alto e basso

per CrossBoard 250 A

NUOVO

Montaggio

CrossBoard® 125A / 250A

gruppo di prodotto 07
sottogruppo prodotto 48
pz/ conf. 1
EAN 4021267015947
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Certificazioni

Norme

IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Omologazioni

UL

for UL feeder circuits >250V

type no.: CR-B-114-A2

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

Omologazione CCC : no certification required

Dati tecnici

Details IEC
Norme
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
Electrical data IEC
corrente nominale (IEC): 320 A
tensione nominale (IEC) AC: 690 V
tensione nominale di isolamento Ui AC: 800 V
tensione di picco Uimp: 6 kV
resistenza nom. alla corrente di picco Ipk max.: 40 kA
Supplementary data IEC

I seguenti valori sono stati rilevati tramite prove con determinate condizioni. Prima di progettare vostro impianto chiedere a Wöhner suddette condizioni.

tensione max. ammissibile (IEC) AC: 800 V
tensione max. ammissibile (IEC) DC: 800 V
corrente d'impiego max. (IEC): 320 A
Details UL
Norme
UL 508
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
corrente nominale (UL): 285 A
tensione nominale (UL) AC: 600 V
frequenza nominale (UL): 50 / 60 Hz
for wires UL: Cu 75°C
SCCR unprotected max.: 10 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
SCCR: 65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC
100 kA with JDDZ fuse Class J 400 A / 600 V AC
Valori meccanici
L x A x P: 114 x 276 x 57
peso: 94.8 kg/100
Poli: 3 poli
grado di protezione dal fronte: IP20
Connessioni
screw clamp connection
screw drive: S4
wire stripping: 30 mm
min. cross-section: 35 mm²
max. cross-section: 150 mm²
Md min.: 4.0 Nm
Md max.: 6.0 Nm
Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
  
min. cross-section UL: AWG 2
max. cross-section UL: MCM 300
torque (UL): 35 - 53 lb-in
for wires UL: Cu 75°C
  

Connecting circular conductors:

35... 50 mm² / 2... 1/0 AWG

4Nm / 35 lb in

 

70... 150 mm² / 2/0 AWG... 300 kcmil

6Nm / 53 lb in

 

35... 95 mm² flexible conductors, circular stranded conductors, flexible conductors with wire-end ferrules DIN 46228-1 max. 30 mm

120... 150 mm² flexible and circular stranded conductors

 

Connecting flexible conductors:

4x - 10x 15,5mm  x 0,8 mm

6Nm / 53 lb in  

Application notes

Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
La capacità di isolamento dell'articolo dipende dalle condizioni di installazione.
for UL feeder circuits >250V

Links

Downloads

Accessori

01654000A
protezione IP20
for round conductors
per: 01594, 01595
NUOVO
Di Più

01655000A
protezione IP20
for flat conductors
per: 01594, 01595
NUOVO
Di Più

Trova il tuo contatto

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com