L'Entreprise
Innovationen
Produits
for UL feeder circuits >250V
The picture may show a similar product.
Référence 31261000A
interrupteur-sectionneur à fusibles D0, pour jeu de barres 3 pôles
pour fusibles D01 et D02
E18 / 63 A / 3P
with electronic fuse monitoring
operator independent switching (snap-action mechanism)
raccordement par le bas
coming soon
Système
CrossBoard® 125A / 250A
Avantages produit
spring terminal enables connection without tools (at first installation)
Groupe de produits | 01 |
Sous-groupe | 51 |
Dimensions de l'emballage | 1 |
EAN | 4021267312619 |
Normes
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approbations
IEC (CB) , VDE , CCC
for fuse links size: | D0 |
fuse links acc. to standard: | IEC / HD 60269-3 |
permitted power dissipation of the fuse-link: | 5,5 W |
Details IEC | |
Normes | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
Courant assigné (IEC): | 35 A |
Tension assignée (IEC) CA: | 400 V |
rated isolation voltage Ui AC: | 500 V |
Tension assignée de tenue aux chocs Uimp: | 6 kV |
Catégorie d'emploi CA: | AC-22B (400 V) |
cond. short-circuit current with fuses (AC): | 50 kA / 400 V |
approved wth fuse links of operation class: | gG |
Supplementary data IEC | |
Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire. |
Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence. |
for fuse links and gauge elements acc. to IEC / HD 60269-3 use of D02 fuse links with silver plated caps is recommended |
|
The function of isolation between incoming and outgoing contacts is provided by the opening of the switching mechanism as required in the standard. |
Charactéristiques mécaniques | |
L x H x P: | 27 x 184 x 100 |
Poids: | 33,0 kg/100 |
Pôles: | 3 pôles |
front degree of protection: | IP20 |
Befestigungsart: Patentierter Rastmechanismus
Points de raccordement | |
spring pulley connection | |
screw drive: | 0,8x4 |
wire stripping: | 12 mm |
min. cross-section: | 1,5 mm² |
max. cross-section: | 16 mm² |
re: | 1.5 - 16 mm² |
rm: | 1.5 - 16 mm² |
rm + AE: | 1,5 - 16 mm² |
f: | 1.5 - 16 mm² |
f + AE: | 1.5 - 16 mm² |
(f + AE may not fit with max. cross-section) | |
Not suitable for aluminium cables ! | |
1,5 - 16 mm² round stranded and flexible without wire-end ferrule |
Not suitable for aluminium cables ! | |
Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence. | |
permitted power dissipation of the fuse-link: | 5,5 W |
Trouver votre contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com